Permit Number: DS08-58
Parcel: 13101023B

Review Status: Completed

Review Details: DEV STDS MODIFICATION REVIEW

Permit Number - DS08-58
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/10/2008 DAVE MANN FIRE REVIEW Approved
12/10/2008 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: David Rivera
Principal Planner
DSD Zoning Review Section
PROJECT: DSMR-08-58
1884 S. Craycroft Road
Quick trip Store No. 1453
Development Standard Modification Request

Transmittal date: December 10, 2008

COMMENTS: Denied

1. Zoning cannot support the DSMR request at this time. It is apparent that there is sufficient room along the north side of the property for a four-foot sidewalk. The parking stalls can be moved westerly a minimum of 6.5 feet to allow for the sidewalk between the parking stalls and the landscape area. The driveway entrance can be modified to allow for clear access due to the relocated parking stalls.




If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.
12/10/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
12/12/2008 MATT FLICK ENGINEERING REVIEW Approved DS 2-08.3.1 -- DSD Engineering has no objection or adverse comment to omission of the sidewalk along the northern parking area.

DS 2-09.4.1 -- DSD Engineering has no objection or adverse comment to locating the bike parking south of the proposed building.
12/15/2008 DCORRAL1 COMMUNITY PLANNING REVIEW Approv-Cond DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Development Standard Modification Request (DSMR)

CASE NUMBER: CASE NAME: DATE SENT

DS08-58 1884 S. Craycroft

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( X) Other - Site Plan

CROSS REFERENCE:

NEIGHBORHOOD PLAN: General Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY December 16, 2008

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

(ΓΌ) DSMR approved with Condition:

1. A striped pedestrian path is preferable to no path being provided. A striped pedestrian path should be proved along the north property line and across parking lot to connect to the building. Also, bollards should be considered at regular intervals along the stripped pedestrian path along the north property line.



REVIEWER: drcorral 791-4505 DATE: 12/15/08
12/15/2008 JOSE ORTIZ TRAFFIC TRAFFIC Approved
12/17/2008 ANDY VERA ENV SVCS REVIEW Approved
12/23/2008 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
CITY OF TUCSON - DEVELOPMENT SERVICES

December 23, 2008

Richard Cordova.
DOWL Engineering
166 West Alameda
Tucson, Arizona 85701

Re: DSMR 08-58 - 1884 South Craycroft Road (D08-0047)

Request: DS 2-09.4.1 - Modify Development Standards to allow class II bicycle parking to be more than 50 feet from the main building entrance.

The Development Standard Modification Request (DSMR) listed above has been APPROVED by the CRDC committee without conditions.


Request: DS 2-08.3.1 - Modify Development Standards to not required the pedestrian circulation path from Craycroft Road.

The Development Standard Modification Request (DSMR) listed above has been DENIED by the CRDC committee per the on-line comments.

PLEASE NOTE THAT A GENERAL NOTE MUST BE ADDED TO THE DEVELOPMENT PLAN WHICH STATES THE DSMR CASE NUMBER, DATE OF APPROVAL, MODIFICATIONS GRANTED, AND CONDITIONS IMPOSED. IN ADDITION, THE CASE NUMBER MUST BE ADDED TO EACH SHEET OF THE DEVELOPMENT PLAN, LANDSCAPE PLAN, AND NPPO PLAN, IN THE LOWER RIGHT CORNER NEAR THE TITLE BLOCK.

If you have any additional questions, please contact me at 837-4919.

Sincerely,

Patricia Gehlen
Zoning/CDRC Manager
Development Services Department

Attachments: 1
XC: file
Records
Fax 624-0384