Review Details: DEV STDS MODIFICATION REVIEW

Permit Number - DS07-15
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2007 MARILYN KALTHOFF START PLANS SUBMITTED Completed
05/07/2007 JIM EGAN FIRE REVIEW Approved
05/11/2007 MATT FLICK ENGINEERING REVIEW Approved DSD Engineering has no objection to approval of a DSMR to allow a PAAL width as narrow as 23'. The Dev. Std. reference quoted by the applicant could not be located. It is believed the correct Dev. Std. is 3-05.2.1.C.1.
05/11/2007 MKALTHO1 COMMUNITY PLANNING REVIEW Approved DEPARTMENT OF URBAN PLANNING & DESIGN

Regarding

SUBJECT: Development Standard Modification Request (DSMR)

CASE NUMBER: CASE NAME: DATE SENT

DS07-15 45 N. Brown Avenue
Jacaranda Village Townhomes

( ) Tentative Plat
(ΓΌ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: NA

NEIGHBORHOOD PLAN: Pantano East Area Plan

GATEWAY/SCENIC ROUTE: NA

COMMENTS DUE BY: 05/14/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( X ) Proposal Complies with Annexation or Rezoning Conditions
( ) Proposal in Substantial Compliance with Plan Policies
( ) Additional Comments
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other


REVIEWER: drcorral 791-4505 DATE: May 10, 2007
05/14/2007 ANDY VERA ENV SVCS REVIEW Approv-Cond 1. ES has no objections to this modification request.

2. However, the approach and access to the refuse enclosures as shown will not work. Recommend repositioning the enclosures, that are by the entrance and to the north of the entrance, at a 30 degree angle to provide for the 14ft x 40ft clear approach. DS 6-01.4.1.C
The enclosures on the west side of the complex do not provide adequate access or maneuverability for refuse service.
DS 6-01.3.1.A , 6-01.4.1.H, and 6-01.4.1.I

Refer to DS section 6-01.0 for compliance for solid waste removal/disposal.
05/16/2007 JOSE ORTIZ TRAFFIC TRAFFIC Approved
05/30/2007 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Denied COMMUNITY DESIGN REVIEW COMMITTEE
CITY OF TUCSON - DEVELOPMENT SERVICES

May 30 2007

Paul Nzomo
Coronado Engineering & Development, Inc.
1630 South Research Loop, Suite #150
Tucson, Arizona 85710

Re: DSMR 07- 15- 45 North Brown Avenue (D03-0007)

Request: DS 3-05.2.1.C.1 -Modify width of PAAL.

The Development Standard Modification Request (DSMR) listed above has been DENIED by the CRDC committee because a Board of Adjustment Variance is required to reduce a PAAL width per LUC Table 3.3.7.I.

PLEASE NOTE THAT THE PLANS SUBMITTED INDICATE CHANGES TO THE DUMPSTERS DATED 10/5/2005 BUT THE ONLY CITY APPROVAL IS DATED 8/11/2003. THE CITY OF TUCSON ENVIRONMENTAL SERVICES DEPARTMENT HAS STATED IN THIS DSMR REVIEW THAT THE APPROACH AND ACCESS TO THE DUMPSTERS (BOTH THOSE BY THE ENTRANCE AND THOSE ON THE WEST SIDE OF THE PROJECT) DOES NOT WORK. PLEASE CONTACT ANDY VERA (791-3171) FOR ADDITIONAL INFORMATION.




If you have any additional questions, please contact me at 837-4919.

Sincerely,


Patricia Gehlen
Zoning/CDRC Manager
Development Services Department

Attachments: 1
XC: file
Records

Fax (520) 723-5394
05/30/2007 PATRICIA GEHLEN ZONING REVIEW Denied The reduction of a PAAL width requires a Board of Adjustment Variance per LUC Table 3.3.7.I.