Permit Number: DP22-0276
Parcel: 12212380A

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP22-0276
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2022 SBEASLE1 START PLANS SUBMITTED Completed
10/03/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review
10/04/2022 LEVANS2 ENGINEERING REVIEW Reqs Change 1. The site is located in a Zone X FEMA floodplain and each building will require a floodplain use permit unless a watershed study proving the property is unaffected by 100-year floods is provided.
2. Provide earthwork cut and fill quantities on the grading page.
3. Per TSM 8-01.5.1. A, multifamily developments with more than six units must provide centralized onsite waste collection service or receive approval for ES for use of individual containers.

4. Spot grades with no change will not allow for drainage flow. Please revise in center of building openings as well as behind buildings.
5. Property located in FEMA Zone X. Floodplain Use permits and elevation certificates will be required for site work and for each building
6. 2-way PAAL width must be at least 24'
7. Nothing may obstruct vehicle operator view in SVT
8. APC's will require ES approval
9. Provide earthwork cut/fill quantities
10. Show Existing and Proposed contours on grading plan
11. First Flush Retention and Balanced Basin Detention requirements must be met
12. All landscaping must be depressed 6-9", not including any DG
13. Show plan for how water will drain from roofs (riprap, etc)
14. Due to extent of grading, please provide a floodplain encroachment analysis in a drainage report showing the Base Flood Elevation will not be raised by more than 2"
15. Update "DP" number on each sheet

Lianne Evans
lianne.evans@tucsonaz.gov
10/04/2022 NMARTEL1 ZONING REVIEW Needs Review
10/07/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Passed