Review Details: GRADING

Permit Number - DP22-0256
Review Name: GRADING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change (The review comments below are from the OK to Submit)

Please revise grading plan:

1. Cut and Fill quantities on page 1 do not match those on page 2, please correct.

2. Provide spot grades and contour lines for proposed grade.

Scott Haseman
scott.haseman@tucsonaz.gov
09/26/2022 ANY ZONING-DECISION LETTER WRITE DECISION LETTER Active
09/28/2022 PAUL CAMARENA ZONING REVIEW Reqs Change 1. Please address Engineering comments.

Loran Shamis
loran.shamis@tucsonaz.gov
10/12/2022 JCARLTO1 NPPO REVIEW Reqs Change CDRC TRANSMITTAL

PROJECT: SFR
ACTIVITY NO. DP22-0256
ADDRESS/PARCEL: 4092 S Melpomene Wy

7.7. Native Plant Preservation
The NPPO is intended to encourage preservation in place of healthy native plants through sensitive site design that minimizes the disruption of areas within the site containing healthy plants while allowing for salvage and transplanting plants on the site that are likely to survive.
A Native Plant Preservation Plan, Section 7.7.4, is required to be submitted and approved or a request for an exception from the Native Plant Preservation requirements approved in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0 prior to Grading Plan approval. Please do not ask for an exception if there are native plants on site.

The easiest way to meet this requirement is to set aside 30% of the lot for Natural Undisturbed Open Space (NUOS). Provide calculations and designate NUOS on the plans.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS:
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff


If you have any questions about this transmittal, contact Matthew Carlton
PDSD Landscape/NPPO Review at email matthew.carlton@tucsonaz.gov