Permit Number: DP22-0191
Parcel: 12406211B

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP22-0191
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2022 SBEASLE1 START PLANS SUBMITTED Completed
09/07/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change (The comments below are from the OK to Submit)

1. Show all easements on the plan. Provide copy of alley abandonment document to show whether any easements remain in effect.
2. Show extent of existing pavement and areas of proposed pavement. Provide barriers to prevent vehicle from driving off paved areas.

Loren Makus
City of Tucson
09/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Azteca Tucson CH 14 – Site Wall
Development Package (1st Review)
DP22-0191

TRANSMITTAL DATE: September 16, 2022

DUE DATE: September 16, 2022

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is August 30, 2023.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0191, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.1 - List as a general note: "Existing zoning is ___."

3. COMMENT: 2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage.

4. COMMENT: 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

COMMENT: 2-06.4.7.A.6.a - As Broadway Blvd. is designated as an Arterial on the COT MS&R Map provide a general note on the cover sheet stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R) & UDC ARTICLE 5.5 GATEWAY CORRIFOR ZONE (GCR)”

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.
5. COMMENT: 2-06.4.9.H.5 – Provide the width of all existing and proposed vehicle access gates, minimum width is 20’ for a two-way access lane, UDC Table 7.4.6-2.

6. COMMENT: Keynote 5 states “(N) 30 FT HT MASONRY PATIO WALLWITH W.I. FENCE (BLACK COLOR) – 5 FT MAX HT”, it appears the “30 FT HT “ is an error but if you are proposing a 30’ it is required to meet perimeter yard setbacks. Clarify what you area proposing.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/26/2022 JPEELDA1 FIRE REVIEW Approved
09/30/2022 AWARNER1 LANDSCAPE REVIEW Needs Review Please provide existing and proposed site/building improvements.
10/03/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change email from: COTDSDPermits
To: Jaca Design
10/03/2022

REVIEW NOTICE

Returned for Corrections: DP22-0191
SITE - Azteca Tucson CH 14. Perimeter wall with fence.
1201 E BROADWAY BL

FEE BALANCE: $ 429.00
ONLINE PAYMENTS
** If the online amount doesn't match "Fee Balance" above, check again in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this blank
4- "Continue"
5- In the Pay column - check the boxes

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on the blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD documents to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)


Sharon Beasley, Certified Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov