Permit Number: DP22-0177
Parcel: 107083180

Address:
770 W GRANT RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP22-0177
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 SBEASLE1 START PLANS SUBMITTED Completed
08/01/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Aztec Transmission
Development Package (1st Review)
DP22-0177

TRANSMITTAL DATE: August 1, 2022

DUE DATE: August 8, 2022

COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is July 20, 2023.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.1 – Provide the name, mailing and email addresses, and phone number of the primary property owner on the cover sheet.

3. COMMENT: 2-06.4.2.D – Provide the page number and the total number of pages in the package (i.e., sheet xx of xx) on all sheets.

4. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0177, adjacent to the title block on all sheets.

5. COMMENT: 2-06.4.4.A – The project location map shall show the subject property approximately centered within the one square mile area

6. COMMENT: 2-06.4.4.C – Label the section corners on the location map.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

7. COMMENT: 2-06.4.7.A.4 – The “PERMITTED USE(S)” is not correct and should be Automotive: Major Service and Repair (excluding bodywork and paint-booths), subject to Use Specific Standards 4.9.13.E.

8. COMMENT: 2-06.4.7.A.6.a – As Grant Rd is designated on the COT MS&R Map as an Arterial provide a general note stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R)”.

2-06.4.7.A.8 - For development package documents provide:

9. COMMENT: 2-06.4.7.A.8.b – Remove the reference to “LOT COVERAGE” from the plan as it is not applicable, see UDC ABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

10. COMMENT: 2-06.4.8.A -

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

11. COMMENT: 2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

12. COMMENT: 2-06.4.9.H.5 – Provide a PAAL width dimension on the plan.

13. COMMENT: 2-06.4.9.H.5 – Provide a fully dimensioned back-up spur at the north end of the parking area, see UDC Article 7.4.6.F.4.

14. COMMENT: 2-06.4.9.H.5 – It appears that vehicle access is proposed around the southwest corner of the Existing Automotive Repair. If proposed provide an access lane width dimension if not demonstrate how vehicles will be prevented from access this area.

15. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculation is not correct. Per UDC Article 7.4.3.F.4 Based on Gross Floor Area (GFA Use the total GFA of all applicable land uses within the development site, plus the area of any outdoor areas necessary to provide the service to the public or conduct the activity. That said the calculation shall include the total GFA of all buildings including the storage container.

16. COMMENT: 2-06.4.9.H.5.d – The bicycle parking space calculation is not correct. Provide the number required and provided for the short- & long-term bicycle parking.

17. COMMENT: 2-06.4.9.H.5.d – Provide a detail for the required long-term bicycle parking that demonstrates how the requirements of UDC Article 7.4.9.D are met.

18. COMMENT: 2-06.4.9.H.5.d – Detail D1 sheet 2 does not match what is shown on sheet 1.

19. COMMENT: 2-06.4.9.H.5.d – Demonstrate on Detail D1 or the plan how the requirements of UDC Articles 7.4.9.B.1.d, & .e are met.

20. COMMENT: 2-06.4.9.L – As it appears that vehicle access will be allowed across the parcel to the east at the southeast corner of this site provide a copy of the recorded cross access easement or agreement with the next submittal.

21. COMMENT: 2-06.4.9.Q – Provide the height of each structure within the foot print.

22. COMMENT: 2-06.4.9.R – Per TSM Section 7-01.4.1.B A sidewalk is required adjacent and parallel to any access lane or PAAL on the side where buildings are located. Show the required sidewalk along the east side of New Storage building.

23. COMMENT: 2-06.4.9.R – If the area around the southwest end of the Existing Automotive Repair is going to provided vehicle access, see comment 14, demonstrate that the existing sidewalk shown on the plan meets the requirements of TSM Sections 7-01.4.2.A & 7-01.4.3.A are met. Also provided the required sidewalk along the west side of the building.

24. COMMENT: 2-06.4.9.R – Per TSM Section 7-01.4.1.C A sidewalk is required adjacent to any parking space accessed by a PAAL where the space is located on the same side of the PAAL as any building and no other parking spaces or PAALs intervene. Show the required sidewalk along the east side of Existing Automotive Repair & Unpermited Addition.

25. COMMENT: 2-06.4.9.R – Per TSM Section 7-01.3.3.B provide the required sidewalk from the existing storage container to the other buildings.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/08/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location of fire hydrants.
b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The points of connection to existing public sewers.
d. Any existing or proposed utility easements
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
08/15/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT:
ACTIVITY NO: DP22-0177
Address: 770 W Grant Rd
Zoning: C-2
Existing Use: Auto Service
Proposed Use: Auto Service

TRANSMITTAL DATE: August 15, 2022
DUE DATE: August 8, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
General Note - UDC 2-10.4.1 Identification and Descriptive Data - All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
1. Arizona Ash is a higher water using plant, and struggles in hotter environments (such as parking areas). Please choose a more appropriate canopy tree.
2. Provide a detail for curb inlets/splash pads to landscape areas on grading and water harvesting plans.
3. Please add a detail to show depressed landscape areas or indicate with notes.
4. Please provide all landscape calculations on the landscape plan, including required trees for the parking areas, Admin. Manual 2-10-4.2.A.2.c and landscape borders, UDC Technical Standards 2-10.4.2.f & g.
5. Please label the existing and future rights of way for all public streets, UDC 7.6.4.C.2.a.
6. An irrigation plan and specifications are required per UDC Administration Manual 2-10.4.2.C and Technical Standards Manual Section 4-01.4.2, Irrigation Standards.
7. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided by labeling it “irrigation only”. UDC Technical Standards 4-01.6.1.A.1.
8. Identify the type of irrigation controller with soil moisture gauge, tensiometer, weather station and/or evaportranspiration data. UDC Tech Standards 4-01.4.A.
9. Provide a detail to show tree planting with root barrier adjacent to walkways.
10. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
08/30/2022 LEVANS2 ENGINEERING REVIEW Needs Review 1. Clarify the purpose of the vehicle use gated area on the southwest side of the building. Reference UBC Table 7.4.6-2 for minimum width of a one-way vehicle access lane. Vehicles cannot back out onto Grant Road. (MS&R)

2. Show on site turnaround in front of each gate (if someone needs to turn around when the gate is closed, after hours for example).

3. Include a contour interval and label all elevation contours.

4. Include landscaping note: depress all water harvesting basins 6”-9"

5. Include page number and total number of pages on each page.

6. Include a note that work in the right of way requires a separate right-of-way permit.

7. Include a detail drawing for 6” depressions in curbs around water harvesting basins.

8. Provide Environmental Services approval for alley trash service.

Lianne Evans
lianne.evans@tucsonaz.gov
09/06/2022 JPEELDA1 FIRE REVIEW Reqs Change Our drawings and water map show that the distance to the fire hydrant is 421 feet, also the closest hydrant is Grant and we will not close down Grant Road. A fire hydrant shall be added and or fire sprinklers shall be installed.

Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Office: 520-837-7033
09/08/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change email from: COTDSDPermits
To: Rick Bright
09/08/2022

Returned for Corrections: DP22-0177
Site/Grading - Aztec Transmission. New storage building added to site (25% increase in building area).
770 W GRANT RD

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on the blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD documents to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)


Sharon Beasley
Certified Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)