Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0170
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 07/18/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | Development Package Comments: Sheet 1 1. Please provide basis of bearing. 2. Provide the name, address, and phone number of the firm who prepared the geotechnical report. 3. Provide 3"x5" box at the lower right quadrant of each sheet for approval stamp. 4. Provide bearings and distances on property lines, typical all sheets. 5. Provide total disturbed area in acres and square feet. 6. Please provide no. of total fixture units in Note 22. 7. Please clarify whether a new trash enclosure will be provided. Provide waste stream calculation. 8. There is 4" PVC private sewer pipe proposed at the Lincoln showroom. Please revise Note 16 regarding no new sewers being proposed. 9. Label APN/owner of current project site and all surrounding properties, typical all sheets. 10. Clearly show and label P/L (suggest to screen back the surrounding properties). Sheet 2 11. Provide bearings and distances for proposed property lines. Sheet 5 12. At NW corner parking, please check surface slope of 1% where TC=99.02 is the same at a few locations. 13. Add SD inlet box symbol to legend. 14. Provide slope at the proposed curb access ramp (where Keynote 5 is labeled at the Hyundai Showroom). 15. Please extend cross section B to cover the full building in N-S direction for the Hyundai Showroom. 16. Label curb opening at SW corner of the Lincoln Showroom Parking. 17. Please reference Detail M on Sheet 8 as it appears in plan. 18. Provide additional flow arrows to show where surface water will flow to in the NE corner of the Lincoln Showroom (at FL=98.30). 19. Please label all existing buildings. 20. Please check parking dimensions of diagonal parking as 13' depth does not meet standard, revise as necessary. 21. Provide FS for all proposed surface parking areas. 22. Provide invert elevation for all inlet boxes. 23. Label slope for curb ramp at ADA access aisles on Lincoln Showroom. 24. Provide additional cross section in E-W direction to include screen wall on Lincoln Showroom. 25. Provide additional TC/FS elevations at ADA access aisles. 26. ADA aisle dimensions do not match with detail M on sheet 8, please revise as necessary. 27. Show curb ramps for proposed ADA access aisles on Hyundai Showroom. 28. Appears to be a non-applicable handicap sign on one of the parking stalls for the Hyundai Showroom. Please review and revise. Sheet 6 29. Please provide additional spot FS at sawcut line. 30. Please check and verify FFE. Sheet 7 31. Please extend Section B in N-S direction. 32. Please verify if wheel stops are necessary or account for a 2.5' vehicle overhang when determining if sidewalk is min 4' clear. 33. Please show minimum and maximum distances on "varies" dimensions. Sheet 9 34. Add existing storm drain and inlet symbol to the legend. Sheet 10 35. Clearly label all existing utilities (storm drain, sewer, water, gas) including pipe size and invert, or reference drawing number where applicable. 36. Please review and revise the length for new sewer pipe from CO#5 to CO #6. Sheet 11 37. Add "Adjust rim to match new pavement" to Keynote 1. Drainage Report Comments: 1. Per Section 2.1.1 of the City of Tucson Standards Manual for Drainage Design and Floodplain Management, a Drainage Report is required for any site greater than one acre. The overall disturbance of this project is over one acre and will require a drainage report. Please revise as necessary. Review and Comments provided by third party engineer reviewers under contract with the City of Tucson. For Questions or Concerns contact: Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 08/05/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Jim Click Lincoln & Hyundai – Tucson Auto Mall Development Package (1st Review) DP22-0170 TRANSMITTAL DATE: August 5, 2022 DUE DATE: August 11, 2022 COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is July 14, 2023. CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0170, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 2. COMMENT: 2-06.4.7.A.4 – Review UDC TABLE 4.8-4: PERMITTED USES - COMMERCIAL AND MIXED USE ZONE, C-3 Zone and provide the Use Specific Standards for a Vehicle Rental and Sales use in the C-3 zone in General Note 3. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 3. COMMENT: 2-06.4.8.A - Provide site boundary perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 4. COMMENT: 2-06.4.9.A – Provide a general note stating, “COVENANT REGARDING DEVELOMENT AND USE OF REAL PROPERTY RECORDED UNDER SEQ # 20180080050” or combine all parcels on this site. 5. COMMENT: 2-06.4.9.H.5 – Provide PAAL and access lane width dimensions for any area where work is proposed. 6. COMMENT: 2-06.4.9.H.5.a – Provide a detail for the proposed angled vehicle parking shown along the west side of Hyundai Showroom. This detail shall include the “A Parking angle”. 7. COMMENT: 2-06.4.9.H.5.a – The provided number of vehicle parking spaces does not include vehicle display spaces. 8. COMMENT: 2-06.4.9.H.5.a – Per the 2018 IBC Chapter 11 Table 1106.1 the required number of accessible vehicle parking spaces is based on the total number of vehicle parking spaces provided. Based on the 1000 spaces proposed shown on the plan this site requires 20 accessible spaces. 9. COMMENT: 2-06.4.9.H.5.a – Provide the number of required and provided van accessible spaces within the vehicle parking spaces calculation. 10. COMMENT: 2-06.4.9.H.5.d – The bicycle parking spaces calculation is not correct. Per UDC Table 7.4.8-1: Minimum Required Bicycle Parking Spaces, RETAIL TRADE USE GROUP, Vehicle Rental and Sales, 2 short-term and 1 space per 12,000 sq. ft. GFA. Minimum requirement is 2 spaces. Maximum requirement is 10 spaces long-term are required. Also, the number proposed was not provided. 2 short-term bicycle parking spaces shall be provided at each new show room building. Clearly show the location on the plan and provide a detail that demonstrates how the requirements of UDC Articles 7.4.9.B.1 & .2 and 7.4.9.C are met. 11. COMMENT: 2-06.4.9.O – The perimeter yard setbacks show under “TABULATONS” are not correct. This site does not does not meet the definition for developing area setbacks. Review UDC Article 6.4.5.C.1 and provide the correct setbacks on the plan. 12. COMMENT: 2-06.4.9.R – Demonstrate that the requirements of TSM Section 7-01.4.1.C is met along the south side of the Lincoln Showroom and the west side of the Hyundai Showroom. 13. COMMENT: 2-06.4.9.R – Provide width dimensions for all new sidewalks on the plan. 14. COMMENT: 2-06.4.9.R – As parking vehicles are allowed to overhang the proposed sidewalks, clearly demonstrate that a parking vehicle does not reduce the side to less than 4’-0” wide. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 08/10/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/18/2022 | AWARNER1 | LANDSCAPE | REVIEW | Approved | |
| 08/25/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/08/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | email from: COTDSDPermits To: Steven Vasquez 09/08/2022 Returned for Corrections: DP22-0170 Site/Grading - Jim Click Lincoln and Hyundai Tucson Auto Mall. Demo two buildings. Construct two new dealership buildings and service building. 660 W AUTO MALL DR Fee Balance: $0 (zero) Thank you for the payment. YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on the blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD documents to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) Sharon Beasley Certified Permit Specialist City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |
| 09/08/2022 | SBEASLE1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Passed | email from: Nicholas Jordan To: CDRC Sept. 15, 2022 In the interest of moving the project forward, please remove me from the review for this project. I will work with the project designer to issue building numbers. Thank you Nicholas Jordan Site Review Project Manager - Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-9623 |