Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0166
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/04/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 07/11/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/12/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Development Package (1st Review) DP22-0 TRANSMITTAL DATE: July 12, 2022 DUE DATE: July 14, 2022 COMMENTS: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 19, 2023. CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.1 -Provide the email address for the Surveyor listed on sheet 1. 2. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0166, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 3. COMMENT: 2-06.4.7.A.6.a – As Broadway Blvd is designated as an Arterial Gateway on the COT MS&R map revise General Note 22 to include “UDC ARTICLE 5.5 GATEWAY CORRIFOR ZONE (GCR)”. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 4. COMMENT: 2-06.4.8.C – Provide dimensioned width of paving, curbs, curb cuts, and sidewalks for both Broadway Blvd & Craycroft Rd on the plan. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 5. COMMENT: 2-06.4.9.H.5 – Demonstrate that the requirements of UDC Article 7.4.6.F.2.a.(2) are met from the drive through to the proposed building. 6. COMMENT: 2-06.4.9.H.5 – Demonstrate that the requirements of UDC Article 7.4.6.F.2.b are met from the drive through lane to the proposed long-term bicycle parking. 7. COMMENT: 2-06.4.9.H.5.d – Detail E sheet 7, the short-term bicycle parking does not match what is shown on sheet 4. 8. COMMENT: 2-06.4.9.R – As parking vehicle are allowed to overhang the sidewalk shown along the north side of the proposed building clearly demonstrate that a minimum 4’-0” sidewalk, TSM Section 7-01.4.3.A, is maintained when a vehicle overhangs the sidewalk 2’-6”, see UDC Article 7.4.6.H.3. 9. COMMENT: 2-06.4.9.R – As parking vehicle are allowed to overhang the sidewalk shown along the west side of the proposed building clearly demonstrate that the 2’-6” overhang does not encroach into the 4’-0” sidewalk. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 07/29/2022 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, RLA PDSD Landscape/Native Plant Preservation Section PROJECT: Chipotle ACTIVITY NO: DP22-0166 Address: 5353 E Broadway Blvd Zoning: C-1 Existing Use: parking area Proposed Use: Food Service TRANSMITTAL DATE: July 29, 2022 DUE DATE: July 14, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. General Note - UDC 2-10.4.1 Identification and Descriptive Data - All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. 1. FYI Engineer & LA - The table in the PCRFCD Manuel can be used in lieu of the Water Budget Table, the only thing that is missing is water demand for plants, which can be added. Make sure units match. 2. A Commercial Rainwater Harvesting plan is required. UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening. This information can be shown on the grading plan. Make sure to show how stormwater is accessing landscape areas (scupper, curb cut, etc.) Show rooftop drainage patterns and show how they are incorporated into the water harvesting calculations. 3. The landscape and grading plans must match. 4. Deeper basins > than 9” deep require something other than d.g.; hydroseed or rock larger than 4” is acceptable. 5. Please remove narrative under “Parking Area Tree Calculation” as that is only one requirement. The tree quantity required is sufficient. 6. Please remove r/w requirements notes if not planting in the right of way. 7. Please label the existing and future rights of way for all public streets, UDC 7.6.4.C.2.a. 8. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided. UDC Technical Standards 4-01.6.1.A.1. 9. Provide a detail to show tree planting with root barrier adjacent to walkways. 10. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package YOUR NEXT STEPS: Submit documents to the Filedrop https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" 1) Comment Response Letter (your response to the reviewer's Requires changes comments) 2) Plan Set (or individual sheets) 3) Any other items requested by review staff If you have any questions, please contact me at anne.warner@tucsonaz.gov |
| 08/08/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 08/24/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. The parking spaces on the north and west sides of the building are shown without wheel stops (minus handicap spaces) show the 4' min width maintained on the adjacent sidewalks with a 2.5' overhang of a parked vehicle. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 08/25/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | email from: COTDSDPermits to: lisa bowers 08/25/2022 REVIEW NOTICE Returned for Corrections: DP22-0166 Site/Grading - Chipotle - Broadway and Craycroft. New restaurant with drive thru. Fee Balance: $0 (zero) YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD documents to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |