Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0136
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 06/08/2022 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | |
| 06/08/2022 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Email from: Jeremy Moore <jmoore3@azdot.gov> To: CDRC Wed 6/8/2022 1:58 PM No comments from ADOT Thanks Jeremy Moore, P.E., Assistant District Engineer 1221 S. 2nd Avenue Tucson, Arizona 85713 520.260.2384 azdot.gov |
| 06/08/2022 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 06/08/2022 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | |
| 06/15/2022 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | June 13, 2022 RE: DP22-0136 Farmington Expo On behalf of Tucson Electric Power (TEP), thank you for the opportunity to comment on this submittal review memorandum. TEP has no objections to this memo. This property is located within TEP’s service territory and will require a new service application from the owner/developer to extend service to the new location. Please call me with any questions or concerns. I can be reached at (425) 633-7431 or via email at Keri.Tallorin@tep.com. Respectfully, Keri Tallorin Land Resources Intern Tucson Electric Power Company a UNS Energy Corporation |
| 06/16/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/17/2022 | SBEASLE1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approved | Approved. See letter in the "Documents" section of PRO: "Tucson Airport Authority, letter of approval, 06.16.22" |
| 06/20/2022 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | email from: Howard Dutt To: CDRC Mon 6/20/2022 1:57 PM No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard Dutt, RLA Project Manager/Landscape Architect Parks and Recreation | City of Tucson Howard.Dutt@tucsonaz.gov main 520.631.2030 |
| 06/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Farmington Expo Development Package (1st Review) DP22-0136 TRANSMITTAL DATE: June 20, 2022 DUE DATE: June 20, 2022 COMMENTS: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 24, 2023. 2-06.3.0 FORMAT REQUIREMENTS 1. COMMENT: 2-06.3.5 – Remove the “DEVELOPMENT PACKAGE PDSD APPROVAL” stamp from all DP sheets. CONTENT REQUIREMENTS 2. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0136, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 3. COMMENT: 2-06.4.7.A.4 – Clarify what the primary use is. “EXPO AREA” is a use classified in the UDC. Also review UDC TABLE 4.8-4: PERMITTED USES - COMMERCIAL AND MIXED-USE ZONES, C-2 Zone and provide the applicable Use Specific Standards. Once the EXPO use is clarified additional comments maybe forth coming. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 4. COMMENT: 2-06.4.9.A – As this site is made up of two (2) parcels, a lot combination is required. Provide a copy of the approved Pima County Assessor’s Combination Request form with the next submittal. 5. COMMENT: 2-06.4.9.F - Clearly show the zoning boundaries where there are two zones, C-2 & R-1. 6. COMMENT: 2-06.4.9.H.5.a – Until comment 2 is addressed vehicle parking requirements cannot be determined. 7. COMMENT: 2-06.4.9.H.5.c - COMMENT: 2-06.4.9.H.5.a – Until comment 2 is addressed loading area requirements cannot be determined. 8. COMMENT: 2-06.4.9.H.5.d - COMMENT: 2-06.4.9.H.5.a – Until comment 2 is addressed bicycle parking requirements cannot be determined. 9. COMMENT: 2-06.4.9.O – The required perimeter yard setback listed for the “REAR” setback is not correct. Per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES, C-2 Zone Nonres Use to a Res Zone the required perimeter yard is 1 ½ (H) = Height of the proposed exterior building wall. 10. COMMENT: 2-06.4.9.O – As no structures are proposed remove all “PROVIDED” setbacks listed. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 06/22/2022 | JPEELDA1 | COT NON-DSD | FIRE | Approved | |
| 07/01/2022 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, RLA PDSD Landscape/Native Plant Preservation Section PROJECT: Farmington Expo ACTIVITY NO: DP22-0136 Address: 1114 S Farmington Rd Zoning: C-2 Existing Use: previously unpermitted graded land Proposed Use: Swap meet, auction TRANSMITTAL DATE: July 1, 2022 DUE DATE: June 16, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. General Note - UDC 2-10.4.1 Identification and Descriptive Data - All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. General Note - Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. 1. The NPPO exception is denied. It's clear from aerials that the existing vegetation on the west side has been cleared and will have to be revegetated, irrigated and hydroseeded. 2. Please label the existing and future rights of way for all public streets, UDC 7.6.4.C.2.a. 3. Please replace the mesquite species with a species without as many issues. Please replace the Jojoba with a faster growing species. 4. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided. UDC Technical Standards 4-01.6.1.A.1. 5. Please add a detail to show depressed landscape areas or indicate with notes. 6. Engineer & LA comment - The table in the PCRFCD Manuel can be used in lieu of the Water Budget Table, the only thing that is missing is water demand for plants, which can be added. Make sure units match. The drainage concept and water harvesting must be designed as a holistic solution. 7. Engineer & LA comment - The grading plan and water harvesting plan do not meet the requirements of the water harvesting ordinance and technical standard. First-flow retention volume requires direction to landscape area and cannot be stored underground. a. The catchment areas must provide water to the infiltration areas. Revise the grading to direct first-flush runoff to the landscape infiltration areas to the maximum extent possible. b. The grading plan needs to reflect the water harvesting basins. c. Water harvesting areas should be depressed between 6 and 9 inches. These areas can be counted toward first flush retention requirements. Do not include small areas such as medians in water harvesting calculations. d. The landscape, water harvesting, and grading plans must match. 8. Engineer & LA comment Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf COT edits - https://www.tucsonaz.gov/files/pdsd/codes/Detention_Retention_Manual_Tech_Standards_Amemdments.pdf RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package YOUR NEXT STEPS: Submit documents to the Filedrop https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" 1) Comment Response Letter (your response to the reviewer's Requires changes comments) 2) Plan Set (or individual sheets) 3) Any other items requested by review staff If you have any questions, please contact me at anne.warner@tucsonaz.gov |
| 08/22/2022 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Completed | |
| 08/23/2022 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Underground retention of the first flush volume is not allowed without prior approval of the Floodplain Administrator. Underground retention will not be supported unless, at a minimum, the following are demonstrated: a. Water harvesting is maximized. Compliance with the Commercial Rainwater Harvesting Ordinance. b. The storage volume must meet both the increased storage volume for detention and the full retention volume. c. Full access for maintenance and sediment removal shall be provided. A system for preventing sedimentation is highly recommended. d. All of the other design qualifications for underground storage in Section 4 of the Detention/Retention manual must be met. 2. Clarify the proposed use. Parking shall meet the vehicle use area design standards, including shade trees or canopies. 3. Once the use has been fully determined and described, additional comments will address the relevant standards. Loren Makus loren.makus@tucsonaz.gov |
| 08/24/2022 | DSTIFFE1 | COT NON-DSD | TRAFFIC | Reqs Change | DP22-0136 Comments: 1. Concrete Header per P.A.G. standard 213. 2. Minimum radius for Header curb returns is 18 Ft. 3. Sight Visibility Triangles are needed with curb returns. (Near side 185 Ft & Far side 110 Ft) David Stiffey DTM Project Coordinator David.Stiffey@tucsonaz.gov |
| 08/26/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: natalee wareham 08/26/2022 REVIEW NOTICE Returned for Corrections: DP22-0136 Site/Grading/Swppp - Farmington Expo. PAD for swapmeet/auction. FEE BALANCE: $ 1,639.00 ONLINE PAYMENTS ** If the online amount doesn't match "Fee Balance" above, check again in a few hours ** https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave this blank 4- "Continue" 5- In the Pay column - check the boxes YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD documents to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |
| 08/26/2022 | SBEASLE1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Passed | Email from: Nicholas Jordan To: CDRC 08/25/2022 Please remove Pima County Addressing from the review queue for this project as it does not require review. Thank you Nicholas Jordan Site Review Project Manager - Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-9623 |