Permit Number: DP22-0131
Parcel: 12803081A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP22-0131
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2022 SBEASLE1 START PLANS SUBMITTED Completed
06/02/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change (These comments are from the OK to Submit)

1. Project proposes fences and gates into multiple properties. Provide recorded easements and/or joint use and joint maintenance agreements.

2. The alley easement is dedicated to the public and utilities. Provide consent to block the easement from City of Tucson Real Estate and from all utilites with facilities within the alley.

Loren Makus
loren.makus@tucsonaz.gov
06/20/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Broadway Shopping Center – Security Gates
Development Package (1st Review)
DP22-0131

TRANSMITTAL DATE: June 20, 2022

DUE DATE: June 15, 2022

COMMENTS: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 17, 2023.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0131, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.6.a – As Broadway Blvd is designated as and Arterial Gateway on the COT MS&R map modify General Note 27 to include UDC Article 5.5 Gateway Corridor Zone (GCZ).

2-06.4.7.A.8 - For development package documents provide:

3. COMMENT: 2-06.4.7.A.8.b – Remove the reference to Site Coverage as it is not applicable in the C-1 Zone, see UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES, C-1 Zone.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

4. COMMENT: 2-06.4.8.A - Provide site boundary perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot,

5. COMMENT: 2-06.4.8.B – Provide the recordation information for the “ALLEY EASEMENT” shown on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

6. 2-06.4.9.H.5.a – If the vehicle parking spaces along the south side of the building are required vehicle parking spaces clearly demonstrate how access will be provided to any customer that wishes to park there.

7. 2-06.4.9.L – As the proposed gate/fence crossed multiple properties some type of easements or agreements are required. Provide copies of the recorded documents with the next submittal.

8. COMMENT: Provide a copy of the last approved site plan that shows the vehicle parking spaces along the south side of the building.

9. COMMENT: Provide written approval for the proposed gate/fence from all entities that have rights to use the existing easement.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/29/2022 AWARNER1 LANDSCAPE REVIEW Approved
07/06/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
to: lisa bowers
Wed 7/6/2022 1:46 PM

REVIEW NOTICE
Returned for Corrections: DP22-0131

Project Description: Site - Broadway Shopping Center, security gates.

FEE BALANCE: $ CREDIT OF -$148.50

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD A RESUBMITTAL to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents


Sharon Beasley, Certified Building Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)