Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - OK TO SUBMIT (GRADING ONLY)
Permit Number - DP22-0107
Review Name: DEV PKG - OK TO SUBMIT (GRADING ONLY)
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2022 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. The site/grading plan must represent the as-built conditions. (https://www.zillow.com/homes/1427-S-Camino-Arriba-Tucson,-AZ-85713_rb/97421285_zpid/) 2. Show the culvert under South Camino Arriba and its outlet. If the outlet remains blocked, provide a release from the Department of Transportation and Mobility. 3. Provide cut and fill quantities. Show pre-development and post-development grades throughout the site. 4. The floor elevation on the plans doesn't match the submitted elevation certificate. Provide consistent documents. 5. The floor elevation on the elevation certificate is not compliant with the City of Tucson and State of Arizona floodplain regulations. Explain how this will be corrected. Loren Makus loren.makus@tucsonaz.gov |
| 05/02/2022 | SBEASLE1 | ZONING-DECISION LETTER | WRITE DECISION LETTER | Passed | |
| 05/02/2022 | LSHAMIS1 | ZONING | REVIEW | Reqs Change | 01. COMMENT: See Engineering comments. |