Permit Number: DP22-0097
Parcel: 112062840

Address:
1929 E GRANT RD

Review Status: Active

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP22-0097
Review Name: DEV PKG - RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2022 SBEASLE1 START PLANS SUBMITTED Completed
10/18/2022 ANY ZONING-DECISION LETTER REVIEW Active
10/18/2022 ANY ZONING REVIEW Active
10/20/2022 JVINCEN1 FIRE REVIEW Reqs Change The seating plan included with this DP does not match the seating plan of the approved construction plans T21CM09431. It appears the total OL will be > 100 which will require fire sprinklers. Your comments on the response letter also state the OL will be > 100. Install fire sprinklers or make revisions to your approved set of construction plans.