Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0095
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 05/24/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Circle D Squared LLC Development Package (1st Review) DP22-0095 TRANSMITTAL DATE: May 24, 2022 DUE DATE: June 02, 2022 COMMENTS: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is April 13, 2023. 2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS 1. COMMENT: 2-06.2.4 – Remove all references to the building codes as a DP is for site related review items only. CONTENT REQUIREMENTS 2. COMMENT: 2-06.4.1 – Provide the email address for the Owner and all Consultants listed on the 1st sheet. 3. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0095, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 4. COMMENT: 2-06.4.7.A.4 – Review UDC Table 4.8-1: PERMITTED USES - RURAL AND SUBURBAN RESIDENTIAL ZONES and provide the Use Specific Standards that apply to both proposed uses. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 5. COMMENT: 2-06.4.9.Q – Provide the square footage, height and specific use of each existing and proposed structure within the footprint of the building(s). 6. COMMENT: Submit the drawings as a single multi-page pdf file. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 05/26/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/09/2022 | AWARNER1 | LANDSCAPE | REVIEW | Approved | |
| 06/22/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Provide documentation that the new building meets the requirements of IFC 2018, Chapter 5, 507.5.1 of 400'. Provide a diagram to TFD from the nearest hydrant to the furthest part of the addition as the hose lays and the distance. If the distance exceeds 400' a fire sprinkler system shall be installed. We will also need documentation that there are two hydrants within in the 400' due to the size and that the fire flow requirement is 2,500 GPM for 2 hours. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 07/27/2022 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/28/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: George Holguin Thu 7/28/2022 8:11 AM REVIEW NOTICE Returned for Corrections: DP22-0095 Site: Circle D Squared. Addition of horse stables and barns to existing residence. 900 N CIRCLE D WY FEE BALANCE: $ 1,450.90 Please pay at a minimum, the REVIEW category fees. A payment is required before your next submittal. ONLINE PAYMENTS ** If the online amount doesn't match "Fee Balance" shown above, check back in a few hours ** https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave this field blank 4- "Continue" 5- In the Pay column - check the boxes 6- "Continue" YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD A RESUBMITTAL to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) - Select "PLANS" for all documents Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |