Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0069
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 04/07/2022 | SBEASLE1 | ENGINEERING | REVIEW | Approved | Engineering was approved by Loren Makus during the OK to Submit. |
| 04/19/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/20/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the existing building sewer that will be under modular building #4 is constructed of materials listed in Table 702.2, IPC 2018. |
| 04/26/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Hydrants shall be shown to meet the IFC 2018, Section 507.5. Provide diagram as the hose lays not the crow flies from the hydrant to the furthest part of the building on the DP. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 05/09/2022 | AWARNER1 | LANDSCAPE | REVIEW | Approved | |
| 06/16/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits to: lisa bowers Thu 6/16/2022 11:21 AM REVIEW NOTICE Returned for Corrections: DP22-0069 Project Description: Site/Grading - International School of Tucson. Two new modular structures. Fee Balance: $0 (zero) Thank you for the payment. YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD A RESUBMITTAL to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff - FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) - Select "PLANS" for all documents Sharon Beasley, Certified Building Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |
| 06/16/2022 | SBEASLE1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Passed | Email from: Nicholas Jordan <Nicholas.Jordan@pima.gov> to: CDRC Tue 6/28/2022 4:04 PM Please remove us from the review from DP22-0069 IST new modular buildings as it does not require review. Thank you Nicholas Jordan Site Review Project Manager - Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-9623 |