Permit Number: DP22-0040
Parcel: 11903430A

Address:
3309 S 12TH AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP22-0040
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2022 SBEASLE1 START PLANS SUBMITTED Completed
03/15/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed Email from: Nicholas Jordan <Nicholas.Jordan@pima.gov>
To: CDRC
Fri 3/11/2022 1:59 PM

DP22-0040
We do not need to review. The project will need to apply for a new address off of W 43rd ST if the primary physical access will be from 43rd.
Thank you.

Nicholas Jordan
Pima County Addressing
03/23/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location of water lines, and fire hydrants.
b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The points of connection to existing public sewers.
d. The locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and streetlights.
e. Any existing or proposed utility easements
f. A legible first floor elevation for the proposed building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
03/23/2022 JPEELDA1 FIRE REVIEW Approved
03/24/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 5 Star Collision – Building Expansion
Development Package (1st Review)
DP22-0040

TRANSMITTAL DATE: March 24, 2022

DUE DATE: March 30, 2022

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is February 24, 2023

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.1 – Provide the email address for the owner listed on sheet 1.

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0040, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. COMMENT: 2-06.4.7.A.6.a - Provide a general note on the cover sheet stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R).

2-06.4.7.A.8 - For development package documents provide:

4. 2-06.4.7.A.8.c – It does not appear that the building area expansion calculation is correct. As parcels 119-03-430A & 119-03-4290 have been operating as separate sites and now you are proposing this as a single site the expansion would be based on the two separate sites or well over 50%, therefore the site is required to meet full code compliance.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

5. COMMENT: 2-06.4.8.C - Provide the following information for both 12th & 43rd Street, and dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

6. COMMENT: 2-06.4.9.A – As this site is made up of two (2) parcels, 119-03-430A & 119-03-4290, a lot combination is required. Provide a copy of the approved Pima County Combo Request form with the next submittal.

7. COMMENT: 2-06.4.9.H.5 – Provide a fully dimensioned vehicle use area for the entire site, this includes the vehicle parking shown on parcel 119-03-430A, see comment 4 above.

8. COMMENT: 2-06.4.9.H.5 – Provide the required 1’-0” setback from the existing canopy called out under Keynote 5 to the proposed PAA, See. UDC Article 7.4.6.F.2.a.(1).

9. COMMENT: 2-06.4.9.H.5 – Fully dimension the required back-up spur at the south end of the vehicle parking area on parcel 119-03-4290.

10. COMMENT: 2-06.4.9.H.5 – Provide a back-up spur at the east end of the vehicle parking area on parcel 119-03-430A.

11. COMMENT: 2-06.4.9.H.5 – Remove the hatching from the northern parking area as the text is very difficult to read.

12. COMMENT: 2-06.4.9.H.5.a – Demonstrate on the plan that any vehicle parking space abutting a vertical barrier, wall, meets the requirements of UDC Article 7.4.6D.2.b.

13. COMMENT: 2-06.4.9.H.5.d – Provide a short- & long-term bicycle parking space calculation that provides the number required and provided for the entire site. Clearly so the location of the required bicycle parking and provide a detail that demonstrates how the requirements of UDC Article 7.4.9 are met.

14. COMMENT: 2-06.4.9.O – Provide a street perimeter yard setback dimension from the proposed building to the outside edge of the nearest adjacent travel lane along 43rd St, see UDC Article 6.4.5.C.2.

15. COMMENT: 2-06.4.9.O – Per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES: C-3 Zone, Nonres Use to a Res Zone the required perimeter yard setback is 1 ½(H) = Height of the proposed exterior building wall. Based on a wall height of 18’-0” the required perimeter yard from the proposed building to the east property line is 27’-0”, proposed setback is 6’-6”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

16. COMMENT: 2-06.4.9.Q – Provide the square footage, & height of all buildings within the foot print.

17. COMMENT: 2-06.4.9.R – Demonstrate on the plan that the requirements of TSM Section 7-01.3.3.B are met.

18. COMMENT: 2-06.4.9.R – Demonstrate on the plan that the requirements of TSM Section 7-01.4.1.A are met.

19. COMMENT: 2-06.4.9.R – Demonstrate on the plan that the requirements of TSM Section 7-01.4.1.C are met along the;
a. East side of the existing building on parcel 119-03-4290
b. Along the south side of the existing office use on parcel 119-03-430A.

20. COMMENT: 2-06.4.9.R – Show the require pedestrian refuge areas along:
a. West side of the proposed building on parcel 119-03-4290
b. Along the south side of the existing body shop use on parcel 119-03-430A.
c.

21. COMMENT: 2-06.4.9.W – Provide a general note stating all signs require separate permits.

If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/02/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: 5 Star Collision
ACTIVITY NO: DP22-0040
Address: 3309 S 12th Ave
Zoning: C-3
Existing Use: Commercial Services
Proposed Use: Commercial Services

TRANSMITTAL DATE: May 2, 2022
DUE DATE: March 30, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. UDC 2-10.4.1 Identification and Descriptive Data - All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

2. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

3. One tree is required for the new parking area on the north, please make sure that it is shading asphalt.

4. A 10’ landscape border is required adjacent to the parking area along W 43rd Ave. Also, a 30” screen is required for parking adjacent to streets.

5. The 5’ landscape border is insufficient unless the intent is to use 5’ of the right of way for landscape. Please clarify.

6. Please label the existing and future rights of way for all public streets, UDC 7.6.4.C.2.a.


7. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided. UDC Technical Standards 4-01.6.1.A.1.

8. Please add a detail to show depressed landscape areas or indicate with notes.

9. Per Admin. Manual 2-10-4.2.D, provide page/detail reference to civil drawings/details that show bike racks, walkways, and screening/retaining walls on landscape plans. See civil drawing is not sufficient.

10. Provide a detail to show tree planting with root barrier adjacent to walkways.

11. A Commercial Rainwater Harvesting plan is required. UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening. Demonstrate how water harvesting is being maximized.

12. Identify the point of drainage off roof areas, amount of flow, and disposition of flow.

13. Identify curb inlets/splash pads to landscape areas on water harvesting or landscape plans.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
05/02/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change A landscape DDO is required for the east side of the property. Notes say that this required interior landscape border is 10', but only measures 6'.
06/20/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change email from: COTDSDPermits
To; Angie
Mon 6/20/2022 3:51 PM

REVIEW NOTICE
Returned for Corrections: DP22-0040

Project Description: Site/Grading - 5 Star Collision Paint & Body Shop. New single-story building, parking, landscape. 3309 S 12TH AV

FEE BALANCE: $ 2,102.38
Please pay at a minimum, the REVIEW category fees.
A payment is required before your next submittal.

ONLINE PAYMENTS
** If amount doesn't match "Fee Balance", check back in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD A RESUBMITTAL to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents

Thank you.
Sharon Beasley, Certified Building Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)
06/20/2022 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Provide sidewalk along 43rd Street. (TS 10-01.3.3)
2. Any proposed required landscaping requires permission from the DTM landscape architect, David Marhefka: David.marhefka@tucsonaz.gov.
3. Provide dimensions for the proposed back-up spur. Show the required barrier free area beyond the end of the spur.
4. Clearly show drainage patterns including roof drainage for the site to demonstrate water harvesting is maximized.

Loren Makus