Permit Number: DP21-0360
Parcel: 20913002A

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP21-0360
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 LOREN MAKUS ENGINEERING REVIEW Denied 1. The plan sheets have multiple parcel identifiers. Please clearly identify the parcel consistently on the plans.
2. The site is within a FEMA Special Flood Harzard Area. Provide a Flood Plain Use Permit from Pima County Regional Flood Control District or provide a letter indicating it is not required.
Loren Makus
loren.makus@tucsonaz.gov
01/10/2022 ELISA HAMBLIN ZONING REVIEW Passed
01/11/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Cathy Russo
cc: Charlie Sulik
Tue 1/11/2022 11:28 AM

Returned for Corrections Notice / Plan Denied for Review
View the ENGINEERING review comments on PRO: www.tucsonaz.gov/pro

NOTE: Please follow the steps below to resubmit your documents for review

Permit/Activity Number: DP21-0360
Project Description: Site - Well Site AV-008A SCADA upgrades.
6050 S CONTINENTAL RD (Pima County)

To view the "Dev Pkg - Okay to Submit" comments by Reviewers:
www.tucsonaz.gov/pro
1. Home page, left side - Activity Search
2. Enter the Activity Number (it’s not case-sensitive)
3. Under "Permits" heading, click on blue tab and you will see different sections
4. Reviews section - click on Review Details
5. Documents section - click on View to the right of each document

YOUR NEXT STEPS
After corrections are made, name your documents as a first submittal (the number one leads the title), for example: 1_Dev Pkg Application.

Upload ALL documents to the Filedrop.
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and if applicable, any notes for our staff


Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services Department
Email: COTDSDpermits@TucsonAz.gov
12/30/2021 SBEASLE1 START PLANS SUBMITTED Completed