Permit Number: DP21-0320
Parcel: 125101480

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP21-0320
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2022 SBEASLE1 START PLANS SUBMITTED Denied
07/12/2022 LOREN MAKUS ENGINEERING REVIEW Denied 1. Clearly show the extent of the canopy relative to the parking stalls. The canopy must be set back at least one foot from the edge of the Parking Area Access Lanes. UDC 7.4.6.F.2.a.

Loren Makus
loren.makus@tucsonaz.gov
07/13/2022 LSHAMIS1 ZONING REVIEW Denied DP21-0320 - Target parking lot improvements

1. See Engineering comment. Demonstrate the parking canopies are setback at least 1' from the edge of the 24' Parking Area Access Lane (PAAL) per UDC 7.4.6.F.2.a.

Loran Shamis
07/15/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Denied email from: COTDSDPermits
To: Devan Peterson
Fri 7/15/2022 9:30 AM

Plan Denied for Review / Request for Resubmittal

View the ENGINEERING review comments on PRO: www.tucsonaz.gov/pro

NOTE: Please follow the steps below to resubmit your documents for review

Permit/Activity Number: DP21-0320

Project Description: Site - Target Store # T-1439, Drive-up expansion. El Con Mall. Restriping 32 parking stalls into 24 drive up stalls with team member loading area and center walkway. Canopies over a portion of the drive up stalls and over the drive aisle.
3699 E BROADWAY BL

PRO
To view the "Dev Pkg - Okay to Submit" comments by Reviewers and your documents:
www.tucsonaz.gov/pro
1. Home page, left side - Activity Search
2. Enter the Activity Number (it’s not case-sensitive)
3. Under "Permits" heading, click on blue tab and you will see different sections
4. Reviews section - click on Review Details
5. Documents section - click on View to the right of each document

YOUR NEXT STEPS
After corrections are made, name your documents again as a first submittal (the number one leads the title), for example: 1_Dev Pkg Application

Upload ALL documents to the Filedrop.
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and if applicable, any notes for our staff


Sharon Beasley, Certified Permit Technician

City of Tucson, Planning and Development Services Department
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)