Permit Number: DP21-0315
Parcel: 13731373A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0315
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/10/2022 JPEELDA1 COT NON-DSD FIRE Approved Add development package case number (DP21-0315), and any other relevant case numbers, including the rezoning case number (C9-12-14) to all sheets of the plan.

Add all rezoning conditions approved with rezoning Ordinance #11137 for rezoning case C9-12-14.

Demonstrate compliance with all rezoning conditions on the DP, including condition number 16, which reads: "Development package shall show cross-access with the residual portion of the subject parcel to the south as shown on the Preliminary Development Plan dated November 26, 2012."
If no cross-access is to be provided, or if any other conditions are not being met, a change of condition and change of PDP must be approved by the Mayor and Council.
01/14/2022 SBEASLE1 COT NON-DSD TRAFFIC Reqs Change Add development package case number (DP21-0315), and any other relevant case numbers, including the rezoning case number (C9-12-14) to all sheets of the plan.

Add all rezoning conditions approved with rezoning Ordinance #11137 for rezoning case C9-12-14.

Demonstrate compliance with all rezoning conditions on the DP, including condition number 16, which reads: "Development package shall show cross-access with the residual portion of the subject parcel to the south as shown on the Preliminary Development Plan dated November 26, 2012."
If no cross-access is to be provided, or if any other conditions are not being met, a change of condition and change of PDP must be approved by the Mayor and Council.
01/14/2022 SBEASLE1 COT NON-DSD TRAFFIC Reqs Change Email from: David.Stiffey@tucsonAz.gov
To: CDRC
Fri 1/14/2022 1:59 PM

DP21-0315

1. Please add the sight visibility triangles for the entrance off of Midvale Park Rd. Near side 185 Ft. Far side is the pedestrian triangle, 30 Ft.


David Stiffey
City of Tucson
Dept. of Transportation & Mobility
01/20/2022 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Add development package case number (DP21-0315), and any other relevant case numbers, including the rezoning case number (C9-12-14) to all sheets of the plan.

Add all rezoning conditions approved with rezoning Ordinance #11137 for rezoning case C9-12-14.

Demonstrate compliance with all rezoning conditions on the DP, including condition number 16, which reads: "Development package shall show cross-access with the residual portion of the subject parcel to the south as shown on the Preliminary Development Plan dated November 26, 2012."
If no cross-access is to be provided, or if any other conditions are not being met, a change of condition and change of PDP must be approved by the Mayor and Council.
01/20/2022 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Email from: Howard Dutt
To: CDRC
Thu 1/20/2022 10:57 AM

No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 631-2030
01/20/2022 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Reqs Change Add development package case number (DP21-0315), and any other relevant case numbers, including the rezoning case number (C9-12-14) to all sheets of the plan.

Add all rezoning conditions approved with rezoning Ordinance #11137 for rezoning case C9-12-14.

Demonstrate compliance with all rezoning conditions on the DP, including condition number 16, which reads: "Development package shall show cross-access with the residual portion of the subject parcel to the south as shown on the Preliminary Development Plan dated November 26, 2012."
If no cross-access is to be provided, or if any other conditions are not being met, a change of condition and change of PDP must be approved by the Mayor and Council.
03/11/2022 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Revise the notes and details in the landscape plan to require depression of landscape areas between 6 and 9 inches in accordance with the retention/detention manual.
2. Show how water harvesting will be maximized. (UDC 7.6.6.C.2)
3. The demolition plan has callouts with no corresponding notes. Please ensure all callouts are consistent with the notes.
4. On the demolition plan, clearly indicate the areas where paving is to be removed.
5. The keynotes listed on GD01 do not have corresponding callouts in the plan view. Show where the applicable features are indicated.
6. Show roof drainage patterns and indicate disposition of the discharge.
7. Clearly label existing and proposed grades throughout the new area of development. Show any areas with more than 2 feet of fill.
8. Additional comments may be forthcoming

Loren Makus
loren.makus@tucsonaz.gov
03/14/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Chris Leon
cc: E. Weber
Mon 3/14/2022 12:23 PM

REVIEW NOTICE
Returned for Corrections: DP21-0315

DESCRIPTION: Site/Grading - Mister Car Wash, AZ 0336. Expand existing parking lot and create a new entrance. 5075 S MIDVALE PARK RD

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff
- Select "PLANS" for all documents for quicker downloading of your documents on our end

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
08/01/2022 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved Approved.
View in DOCUMENTS section of PRO, titled, "Tucson Electric Power, approval letter, 07.25.22", and "Tucson Electric Power, facilities map, 07.25.22"
12/06/2021 SBEASLE1 COT NON-DSD REVIEW Approved Add development package case number (DP21-0315), and any other relevant case numbers, including the rezoning case number (C9-12-14) to all sheets of the plan.

Add all rezoning conditions approved with rezoning Ordinance #11137 for rezoning case C9-12-14.

Demonstrate compliance with all rezoning conditions on the DP, including condition number 16, which reads: "Development package shall show cross-access with the residual portion of the subject parcel to the south as shown on the Preliminary Development Plan dated November 26, 2012."
If no cross-access is to be provided, or if any other conditions are not being met, a change of condition and change of PDP must be approved by the Mayor and Council.
12/06/2021 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
12/06/2021 SBEASLE1 COT NON-DSD REVIEW Approved Email from: Bea Paulus
To: CDRC
Mon 12/6/2021 12:51 PM

Depending on where this new entrance is going, there may be a conflict with the Sun Tran bus stop on Irvington at Midvale Park SE corner. But, it looks like we will be OK. Thank you.

Bea Paulus, Programs & Projects Manager
Sun Tran / Transit
520-206-8826, bea.paulus@tucsonaz.gov
12/06/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
12/06/2021 SBEASLE1 START PLANS SUBMITTED Completed
12/06/2021 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
12/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Mister Carwash AZ 0336
Development Package (1st Review)
DP21-0315

TRANSMITTAL DATE: December 23, 2021

DUE DATE: December 27, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is November 21, 2022.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.5 – Remove the old “DEVELOPMENT PACKAGE PDSD APPROVAL” stamp from the plan as it is no longer used. An Electronic Stamp will be applied once the plan is approvable.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.1 – Provide the email addresses, and phone number of the owner listed on the cover sheet.

3. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0315, and rezoning case number, C9-12-14, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

4. COMMENT: 2-06.4.7.A.3 – Provide the rezoning, C9-12-14, conditions on the plan.

5. COMMENT: 2-06.4.7.A.3 – The proposed changes to this site do not match the last submitted preliminary development plan (PDP). Contact John Beall, Rezoning Section, and request written conformation that the proposed development is in compliance with the PDP. A Change to PDP may be required.

6. COMMENT: 2-06.4.7.A.4 – The use listed under General Note 3 is not correct and should be listed as Automotive: Minor Service and Repair, Automotive Washing - Self Service, Subject to Use Specific Standard 4.9.13.E.

7. COMMENT: 2-06.4.7.A.6.a – General Note 22 remove the reference to “UDC ARTICLE 5.5 GATEWAY CORRIDOR ZONE (GCZ)” as this site does not boarder on a street designated on the COT MS&R map as a Gateway.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

8. COMMENT: 2-06.4.8.C - The following information regarding Irvington & Midvale Park, dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

9. COMMENT: 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

10. COMMENT: 2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

11. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculation is not correct. Per UDC TABLE 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED, COMMERCIAL SERVICES USE GROUP, Automotive Washing, Self-Service, 0 spaces are required. The UDC does not reference the number of employees for the proposed use.

12. COMMENT: 2-06.4.9.H.5.d - The bicycle parking space calculation is not correct. Per UDC TABLE 7.4.8-1: MINIMUM REQUIRED BICYCLE PARKING SPACES, COMMERCIAL SERVICES USE GROUP, Car Wash, Self-Service, none required. If you are going to provide short-term bicycle parking as stated in the calculation, clearly show the location on the plan and provide a detail the demonstrates how the requirements of UDC Articles 7.4.9.B & .C are met.

13. COMMENT: 2-06.4.9.J – Show the future curb & sidewalk for both Irvington & Midvale Park on the plan.

14. COMMENT: 2-06.4.9.O – As the existing curbs along Irvington & Midvale Park are not at future location the required street perimeter yard setbacks listed under General Note 18 need to reference back of future curb.

15. COMMENT: 2-06.4.9.O – The “105’ MAJOR STREET AND ROUTE SETBACK for both Irvington & Midvale Park shown on the plan is not correct. Per UDC Article 6.4.5.C.2 & Table 6.4.5.C-1 the street perimeter yard setbacks are measured from the back of future curb and based on the height of the structure.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/24/2021 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change (This letter can be viewed as a PDF. See the "Documents" section of PRO: "TAA, review comments, first submittal, 12.21.21")

Email from: Scott Robidoux <srobidoux@flytucson.com>
To: CDRC
Cc: E. Weber
Tue 12/21/2021 4:09 PM

Attached is a copy of my comment letter on DP21-0315. I have included the applicant on this email so they may receive a copy of my comment letter, the TAA Avigation Easement document, and the Airport Disclosure Statement form.
Thank you,
Scott Robidoux, C.M., Manager of Planning

TUCSON AIRPORT AUTHORITY
7250 South Tucson Boulevard, Suite 300
Tucson, AZ 85756
Phone 520-573-8100, Direct 520-573-4811
12/29/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Mister Car Wash Expansion
ACTIVITY NO: DP21-0232
Address: 5075 S Midvale Park Rd
Zoning: C-2
Existing Use: Car wash, vacant, graded
Proposed Use: Automotive Services, Car wash expansion

TRANSMITTAL DATE: December 29, 2021
DUE DATE: December 27, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. Landscape Notes reference the LUC, please provide current code UDC references,.

2. Additional plants are required to meet the required 50% vegetative cover at two years growth, for the street landscape border, UDC 7.6.4.C.2.e.

3. A 5’ wall is required adjacent to residential uses, UDC table 7.6.4-1.

4. Please label the existing and future rights of way for S Midvale Park Rd UDC 7.6.4.C.2.a.

5. Please add/call out soil moisture gauge/tensiometers and rain shut-off device on irrigation plans and details. UDC Tech Standards 4.01-2.A.

6. The aerial provided with the native plant exception, shows what appears to be palo verdes. Please provide additional information on how they will be protected during construction, as they are shown to remain and are counted towards landscape border requirements. If part of the landscape border, the irrigation plans needs to show the trees are being irrigated (revise poly).

7. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.

8. A Commercial Rainwater Harvesting plan is required to meet 50% of the landscape water needs. UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening.

9. Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. Please show how this plan works with existing development. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf

10. Grading, hydrology, and landscape plans must be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. UDC 7.6.6.C.2. The landscape, water harvesting, and grading plans must match.

11. Identify the point of drainage off roof areas, amount of flow, and disposition of flow.

12. Identify curb inlets/splash pads to landscape areas on water harvesting or landscape plans.

13. Indicate basin inlets/outlets on both landscape and water harvesting plans. Provide spot elevations.

14. Retention/detention basins should be designed naturally and organically, whenever practicable. Squares and rectangles are not considered organic shapes.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov