Permit Number: DP21-0283
Parcel: 13337160A

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP21-0283
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2021 SBEASLE1 START PLANS SUBMITTED Completed
10/29/2021 ELISA HAMBLIN ZONING REVIEW Denied Submit a development package which meets the standards of Administrative Manual 2-06. See Engineering comments for additional requirements.

-Elisa Hamblin, AICP
Site Review Section Manager
11/09/2021 LOREN MAKUS ENGINEERING REVIEW Denied 1. The 100-year discharge at this location is estimated at about 200 cubic feet per second. Provide engineering analysis that the culvert will have capacity for the discharge.
2. Provide construction details for the culvert. Show how the culvert relates to the existing conditions including the invert of the culvert compared to the surface of the driveway.
3. Show extent of driveway improvements including fill and protection of the fill from erosion.
4. A floodplain use permit is required for this project. Apply for a floodplain use permit for this project.
Loren Makus
loren.makus@tucsonaz.gov
11/10/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Michael Aragon
Cc: ADDcpn, Aragon Underground
Wed 11/10/2021 9:53 AM

Returned for Corrections Notice / Plan Denied for Review
View the ZONING and ENGINEERING review comments on PRO: www.tucsonaz.gov/pro
(all documents are attached for reference)

NOTE: Please follow the steps below to resubmit your documents for review

Permit/Activity Number: DP21-0283
Project Description: Site - Culvert install on dirt road. 365 N TANQUE VERDE LOOP RD

To view the "Dev Pkg - Okay to Submit" comments by Reviewers and your documents:
www.tucsonaz.gov/pro
1. Home page, left side - Activity Search
2. Enter the Activity Number (it’s not case-sensitive)
3. Under "Permits" heading, click on blue tab and you will see different sections
4. Reviews section - click on Review Details
5. Documents section - click on View to the right of each document

YOUR NEXT STEPS
After corrections are made, name your documents as a first submittal (the number one leads the title), for example: 1_Dev Pkg Application.

Upload ALL documents to the Filedrop.
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and if applicable, any notes for our staff


Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services Department
Email: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)