Permit Number: DP21-0271
Parcel: 127122700

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP21-0271
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2022 SBEASLE1 ENGINEERING REVIEW Approved Engineering was approved for this revision by Loren Makus during the recent OK to Submit.
07/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The routing of the building sewer and the location of the gas meter as shown on the revised site plan are radically different from those shown on the revised plumbing drawings for the tenant improvement. Which is correct?
2. The "vault", keynote 17, is actually a gravity grease interceptor and should be labeled correctly.
07/13/2022 STEVE SHIELDS ZONING REVIEW Approved
07/18/2022 AWARNER1 LANDSCAPE REVIEW Approved
08/08/2022 JPEELDA1 FIRE REVIEW Approved
08/09/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
to: lisa bowers
08/09/22

REVISION REVIEW NOTICE

Returned for Corrections: DP21-0271
Site - Gyroshack. Relocate the dumpster.

REVISION FEE BALANCE: $ 511.50
Please pay at a minimum, the REVIEW category fees.
A payment is required before your next submittal.

ONLINE PAYMENTS
** If the online amount doesn't match "Fee Balance" shown above, check back in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set or individual revised sheets
- Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents


Sharon Beasley, Certified Permit Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)