Permit Number: DP21-0259
Parcel: 141366860

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP21-0259
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2022 SBEASLE1 START PLANS SUBMITTED Completed
01/27/2022 SBLOOD1 ENGINEERING REVIEW Approved
02/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the need for backwater valves for lots 86, 89, and 90 in parcel 7 and lot 38 in parcel 8. Each of these lots appear to have a FFE more than 12" above the rim elevation of the next upstream manhole. [Initial comment: Revise the site drawing to indicate for which lots backwater valves will be required because the rim elevation of the next upstream sanitary manhole is less than 12" below the proposed first floor elevations. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.]
02/15/2022 SBEASLE1 PIMA COUNTY ADDRESSING Approved Email from: <Addressing@pima.gov>
To: CDRC
cc: Andie Hemmah
Mon 2/14/2022 4:33 PM

Pima County Addressing approves La Estancia, Tentative Plat, 2nd Submittal Review: DP21-0259.

Thank you
Nicholas Jordan, Addressing Specialist

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701, (520) 724-9623
02/16/2022 SBEASLE1 COT NON-DSD TRAFFIC Reqs Change Email from: David.Stiffey@TucsonAz.gov
To: CDRC
Tue 2/15/2022 11:19 AM

DP21-0259

Sheets 7 and 8:
Please add Sight Visibility Triangles where project entrances intersect with Camino Boleadoras. Include lengths.
02/28/2022 STEVE SHIELDS ZONING REVIEW Approved
03/23/2022 AWARNER1 LANDSCAPE REVIEW Needs Review
03/23/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Andie Hemmah
Wed 3/23/2022 5:13 PM

REVIEW NOTICE
Returned for Corrections: DP21-0259

DESCRIPTION: Tentative Plat - La Estancia, Parcels 6 thru 8. 6670 E CAMINO BOLEADORAS

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your THIRD submittal documents accordingly, example: 3_Comment Response Letter

FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff
- Select "PLANS" for all documents for quicker downloading on our end

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
03/23/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change Fire department access road dead ends. IFC 2018, Appendix D, D103.4 Dead ends. Dead-end fire apparatus access roads in excess of 150 ft shall be provided with width and turn around provisions in accordance with Table D103.4. Cul-de-Sac shall have a 96 foot diameter from curb to curb. COT uses the UDC and the IFC shall take precedence on the dead-end cul-de-sac.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner