Permit Number: DP21-0256
Parcel: 124190600

Address:
887 S WARREN AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0256
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2021 SBEASLE1 START PLANS SUBMITTED Completed
10/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Peak Corrosion Control, Inc – New 5,000 SF Building
Development Package (1st Review)
DP21-0256

TRANSMITTAL October 15, 2021

DUE DATE: October 25, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 19, 2022.

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

1. COMMENT: 2-06.2.2 – The development package shall be submitted as a multi-page single PDF file.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0256, adjacent to the title block on all sheets.

3. COMMENT: 2-06.4.4.C – Provide the section, township, and rang, and label the section corners on the location map.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

4. COMMENT: 2-06.4.7.A.2 – Provide the square footage of the site in General Note 5.

5. COMMENT: 2-06.4.7.A.4 – Under General Note 2 you list a use of “COMMERCIAL SERVICES OFFICE AND STORAGE” Storage is not part of the Commercial Services Use Group. You also list “SERVICE BAY” as a use which implies some type of repair use. Clarify what the primary use is. Following discussion with staff it appears that the use should be something along the lines of Engineering firm (office) and Construction Services.

6. COMMENT: 2-06.4.7.A.4 – Once you determine the /existing/proposed use review UDC TABLE 4.8-5: PERMITTED USES - INDUSTRIAL ZONES * and provide all applicable Use Specific Standards within General Note 2.

2-06.4.7.A.8 - For development package documents provide:

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

7. COMMENT: 2-06.4.8.B – If applicable show all easements of record on the plan along with the recordation information.

8. COMMENT: 2-06.4.8.C - The following information for Warren Ave shall be provided on the plan: right-of-way width, dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

9. COMMENT: 2-06.4.9.A – As this site is made up of numerous parcels a lot combination is required. Provide a copy of an approve Pima County Assessor’s Combo Request form with the next submittal.

10. COMMENT: 2-06.4.9.F – Provide the zoning for the property to the east.

11. COMMENT: 2-06.4.9.H.5 – As the proposed building expansion requires that the entire site be brought up to code for UDC Article 7.4, see UDC Article 7.4.3.E.2 provide fully dimensioned existing/proposed vehicle use areas. Additional comments maybe forth coming.

12. COMMENT: 2-06.4.9.H.5 – Demonstrate that all vehicle use areas, existing/proposed, meet the requirements of UDC Article 7.4.6.I.

13. COMMENT: 2-06.4.9.H.5.a – Until the primary use is clarified, see comment 5, Zoning cannot verify vehicle parking requirements.

14. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculation shall include the number of required/provided accessible spaces to include the number of required/provided van accessible spaces.

15. COMMENT: 2-06.4.9.H.5.c - Until the primary use is clarified, see comment 5, Zoning cannot verify loading space requirements.

16. COMMENT: 2-06.4.9.H.5.d - Until the primary use is clarified, see comment 5, Zoning cannot verify bicycle parking space requirements. Once clarified provide a short- & long-term bicycle parking space calculation that provides the number required and provided. Also, a short- & long-term bicycle parking space details will be required. These details shall demonstrate how the requirements of UDC Articles 7.4.9.B, .C & .D are met.

17. COMMENT: 2-06.4.9.Q – Provide the height and use of each building within the footprint.

18. COMMENT: 2-06.4.9.R – – As the proposed building expansion requires that the entire site be brought up to code for TSM Section 7, see TSM Section 7-01.2.B.2. provide fully dimensioned existing/proposed pedestrian circulation. Additional comments maybe forth coming.

19. COMMENT: 2-06.4.9.R – Demonstrate that the requirements of TSM Section 7-.1.4.0 are met for the proposed building.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/20/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, PLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Peak Corrosion Control, Inc.
ACTIVITY NO: DP21-0256
Address: 887 S. Warren Ave.
Zoning: I-1
Existing Use: Warehouse facilities
Proposed Use: Warehouse facilities

TRANSMITTAL DATE: October 20, 2021
DUE DATE: October 25, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

2. 7.6 Landscaping and Screening - The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2.

3. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.Please provide all landscape calculations on the landscape plan, including required trees for the parking areas, Admin. Manual 2-10-4.2.A.2.c and landscape borders, UDC Technical Standards 2-10.4.2.f & g.

4. Please label the existing and future rights of way for S Warren Ave, UDC 7.6.4.C.2.a.


5. A Commercial Rainwater Harvesting plan is required UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening.

6. Grading, hydrology, and landscape plans must be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. UDC 7.7.6.C.2. The landscape and grading plans must match.

7. Identify the point of drainage off roof areas, amount of flow, and disposition of flow. Identify curb inlets to landscape areas.

8. Retention/detention basins should be designed naturally and organically, whenever practicable.

9. Modify details to show depressed landscape areas.

10. Identify water meter and POC on irrigation plan.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
10/21/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/03/2021 JPEELDA1 FIRE REVIEW Approved
12/02/2021 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review Email from: <Addressing@pima.gov>
To: CDRC
Thu 12/2/2021 10:16 AM

This project has an outstanding balance. The invoice for DP21-0256 has not been paid so the review has not been started.

I will schedule the review after fees are paid (by the applicant).

Thank you
Nicholas Jordan, Addressing Specialist

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-9623
12/22/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Revise the pedestrian crossing so the crosswalk doesn't pass directly behind parking spaces.
2. Show the solid waste storage and service locations. Provide waste stream calculations demonstrating adequate capacity.
3. Show roof drainage patterns for the new building. Make sure roof drainage is not directed to sidewalk areas unless it is directed through scuppers.

Loren Makus
loren.makus@tucsonaz.gov
12/27/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Martin Stickley
Mon 12/27/2021 8:15 AM

Returned for Corrections: DP21-0256
DESCRIPTION: Site: Peak Corrosion Control. Storage building. 887 S WARREN AV

FEE BALANCE: $ 1,206.50
Please pay at a minimum, the REVIEW category fees.
A payment is required before your next submittal.
ONLINE PAYMENT
If amount doesn't match "Fees Due", check back in a few hours
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP for your Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff


Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)