Permit Number: DP21-0247
Parcel: 10707016F

Address:
1306 W GRANT RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0247
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2022 SBEASLE1 START PLANS SUBMITTED Completed
08/23/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Tucson Gas Station – 1306 W Grant Rd – I-1
Development Package (4th Review)
DP21-0247

TRANSMITTAL DATE: August 23, 2022

DUE DATE: September 06, 2022

COMMENTS: Please resubmit revised drawings with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 13, 2021.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

1. This comment was not correct. Per UDC Article 7.4.6.H.3. the dimension should be 2’-6” not 2’-01/2” as shown on detail 1 sheet SP@. COMMENT: 2-06.4.9.H.5.a – Detail 1 sheet SP2 the wheel stop location dimension is not correct, review UDC Article 7.4.6.H.3 and provide the correct dimension. Sheet C)2 shows the correct dimension. This detail also is not to scale and the dimensions provided are not correct.

2. This comment was not addressed correctly. Sheet SP1 shows 2 racks so the provided number should be 4 not 2 as shown. COMMENT: 2-06.4.9.H.5.d – The bicycle parking calculation has been removed from the plan. Provide a bicycle parking space calculation that provides the number required and provided. Based on the 2 racks called out under Keynote 21 sheet SP1 the number provided should be 4, UDC Article 7.4.9.B.2.d “a single rack is designed and located to accommodate two bicycles”.

3. This comment was not addressed. Detail 11, sheet SP@ does not address the requirements of UDC Article 7.4.9.B.1.e, “Outdoor bicycle parking areas must be lighted so that they are thoroughly illuminated and visible from adjacent sidewalks , parking lots , or buildings during hours of use.” COMMENT: 2-06.4.9.H.5.d – Demonstrate on the plan/detail how the requirement of UDC Article 7.4.9.B.1.e is met.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/31/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The gas station was connected to the 42" interceptor in 1994 when the interceptor was built. The rim elevation and FFE shown on your development plan indicates that a backwater valve will be required. See https://onbase.pima.gov/publicaccess/WW_NextGen_Single/etc/cq/results.html?cqid=161&OBKey__157_1=G%2D94%2D023
[Second comment: Comment not addressed on SP-1 or SP-3.] [Initial comment: Provide the rim elevation of manhole 6677-OUTADOT and the first floor elevation of the building. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.]
09/13/2022 JGARCIA9 ENGINEERING REVIEW Reqs Change 1. Single Container Enclosure shown, keynotes 6 & 7 on sheet SP2 indicate the need for a Double Container Enclosure. Please revise as a Double Container Enclosure per TSM 8-01.9.0 Figure 3A.
2. Detail 10 on sheet SP2 does not meet TSM 8-01.9.0
Figure 2. Please revise Wall and Footing dimensions and reinforcing accordingly. Footing Dimensions and reinforcing incorrect, wall reinforcing & grouting note missing.
3. Keynote 14 located in SE Landscape area. Please re-label correctly or remove.
Joshua Garcia
joshua.garcia@tucsonaz.gov
09/16/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change email from: COTDSDPermits
To: Alexis Gallegos
09/16/2022

Returned for Corrections: DP21-0247
SITE - Tucson Gas Station, Store Retrofit.
1306 W GRANT RD

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on the blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your FIFTH submittal documents accordingly, example: 5_Comment Response Letter

3. UPLOAD documents to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)


Sharon Beasley
Certified Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)