Permit Number: DP21-0229
Parcel: 12912100A

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0229
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2022 SBEASLE1 START PLANS SUBMITTED Completed
03/01/2022 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approv-Cond Approved conditionally.
The letter can be viewed on the "Documents" section of PRO: "Tucson Airport Authority, approval letter, 02.27.22"
03/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: New Office Construction – 1001, 1015 & 1019 E Silverlake Rd
Development Package (2nd Review)
DP21-0229

TRANSMITTAL DATE: March 8, 2022

DUE DATE: March 03, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 30, 2022.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

1. This comment was not addressed, add UDC Article 5.4 to the Second Site Note 17. COMMENT: 2-06.4.7.A.6.a – Second Site Note 17 provide the applicable UDC Article that applies to the MS&R.

2-06.4.7.A.8 - For development package documents provide:

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.
2. This comment was not fully addressed. Provide a dimension from center line of both streets to the curb. COMMENT: 2-06.4.8.C - The following information regarding right-of-way adjacent to the site shall be provided: the name, right-of-way width and dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

3. This comment was not addressed. COMMENT: 2-06.4.9.H.2 – As future curbs have not been shown for both Park & Silverlake show future curb, see comment 19 below and provide future sight visibility triangles on the plan. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

4. This comment was not addressed there is nothing preventing access to the alley. COMMENT: 2-06.4.9.H.5 – Alley access or egress is not allowed, see UDC Article 7.4.6.K, a Board of Adjustment for Variance will be required to use the alley to egress the vehicle parking area.

5. This comment was not addressed. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.F.2.b Access lanes and PAALs must be setback at least two feet from a wall, screen, or other obstruction over six inches. That said, show the 2’ setback along the west side of the proposed parking area access lane to the proposed wall.

6. As width dimensions were not provided Zoning cannot verify if the requirement is met. COMMENT: 2-06.4.9.H.5.a – Per 2018 IBC Chapter 11 Section 1106.5 the accessible parking space is required to be a van accessible space. Demonstrate on the plan/detail that the requirements of ICC A117.1, Section 502.2 are met.

7. This comment was not addressed. The only vehicle parking spaces shown on the plan are 90 degreee parking spaces. COMMENT: 2-06.4.9.H.5.a – Keynote 15 talks about “PARALLEL SPACES” but there are no parallel spaces shown on the plan.

8. This comment was not addressed. COMMENT: 2-06.4.9.H.5.d – Demonstrate on Detail 5 sheet C2 how the requirements of UDC Articles 7.4.9.B.1.d & .e, 7.4.9.B.2.f, .g & .h are met.

9. Based on the bicycle parking calculation you are proposing to provide long term bicycle parking, provide a detail that demonstrates how the requirements of UDC Article 7.4.9.D are met. COMMENT: 2-06.4.9.H.5.d – For your information per UDC Article 7.4.8.B.1.a.(1) No long-term bicycle parking is required on a site where there is less than 2,500 square feet of gross floor area.

10. This comment was not addressed. COMMENT: 2-06.4.9.J - If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc.)

11. Zoning acknowledges that Site Note 15 was modified but the street perimeter yard setbacks shown on the plan are not correct. Show the future curbs for both Silverlake & Park on the plan and provided a setback dimension from the back of future curb to the building. COMMENT: 2-06.4.9.O – The setback listed under Site Note 15 is not correct. Per UDC Article 11.4.6 definition of Established Area Setback streets that are designated a Major route by the COT MS&R plan do not qualify for established are setbacks. That said the street perimeter yard setbacks for this project are based on UDC Article 6.4.5.C.2 & TABLE 6.4.5.C-I, ADT of 1,000 or greater and shall be 21’ or the height of the proposed exterior wall, greater of the two, measured to back of future curb. Show the future curb on the plan and provide the applicable street perimeter yard setbacks.

12. This comment was not addressed no sidewalk is provided to Park. COMMENT: 2-06.4.9.R – Clearly demonstrate that the requirements of TSM Section 7-01.4.1.A are met, At least one sidewalk is required to a project from each street on which the project has frontage, unless there is no vehicular access from a street because of a physical barrier, such as a drainageway or an unbroken security barrier (e.g., a wall or fence).

Addition comments due to changes to the drawings:

13. COMMENT: 2-06.4.9.H.5 – Provide a PAAL width dimension for the proposed vehicle use area.

14. COMMENT: 2-06.4.9.H.5.a – The wheel stop location dimension shown on the parking space details is not correct. Review UDC Article 7.4.6.H.3 and provide the correct dimension.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/10/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change Fire department access lane shall be 20' wide per IFC 503.2.1
Distance to nearest hydrants shall be shown as the hose lays not the crow fly's.
Plans show that TFD provided residual and static pressure. TFD does not provide data but Tucson Water.
Plans show that the building is having fire sprinklers installed but does not show a new underground fire line

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
TFD Fire Plans Examiner
520-837-7033
04/01/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Office Building
ACTIVITY NO: DP21-0229
Parcel: 129-12-101A
Zoning: C1/2
Existing Use: vacant, truck storage
Proposed Use: Office

TRANSMITTAL DATE: April 1, 2022
DUE DATE: March 3, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.

1. This comment was not addressed - Please label the existing and future rights of way for Silverlake Rd and Park Ave. UDC 7.6.4.C.2.a.

2. This comment was not adequately addressed - Locate all existing plants in the r/w along Park Ave. and Silverlake Rd. and indicate if they are to remain. These plants can count towards the landscape border requirement.

3. This comment was not addressed - Plant symbols do not reflect the correct size of the plants.
4. This comment was not addressed - The landscape border along Silverlake Rd. needs to continue the whole length of the parcel. Existing plants can be counted towards meeting this requirement.

5. This comment was not adequately addressed - Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.

6. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided. UDC Technical Standards 4-01.6.1.A.1.

7. This comment was not addressed - Commercial Rainwater Harvesting plan is required UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening.

8. This comment was not adequately addressed - Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design.
https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf

9. This comment was not adequately addressed - Grading, hydrology, and landscape plans must be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. UDC 7.7.6.C.2. The landscape and grading plans must match.

10. This comment was not adequately addressed - Identify the point of drainage off roof areas, amount of flow, and disposition of flow.

11. This comment was not adequately addressed - Identify curb inlets to landscape areas.

12. This comment was not adequately addressed - Modify details to show depressed landscape areas. There are conflicts in the notes, minimum depressions for water harvesting are 6”.

13. This comment was not addressed - The parking area does not meet the intent of the UDC in terms of including trees in the parking lot to shade the asphalt. The intent is to provide as much shade on the asphalt as possible, and the requirement is 1 tree per 4 parking spaces; trees are expected to be placed within the parking area itself. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.

14. This comment was not adequately addressed - Please add/call out soil moisture gauge/tensiometers and rain shut-off device on irrigation plans and details. UDC 4.2.A.

15. This comment was not adequately addressed - Provide a detail to show tree planting with root barrier adjacent to walkways.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
04/05/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Future sidewalk, future right of way lines, and future sight visibility triangles are still not being shown. Revise plans accordingly and note that S Park Av is an arterial street and according to TSM section 10-01.5.3 for drive/paal to arterial - near side is 345 and far side 125.
2. Pedestrian connection still not being shown from proposed office building out to S Park Av. Revise plans as necessary.
3. Drainage arrows still not matching the proposed grades. From looking the spot grades little to no runoff will make into the water harvesting area on the northwest of the parking area and no runoff will pass through the curb cuts on the southwest landscaped area (which is also not being shown as depressed for water harvesting). Revise as needed.
4. Show point of discharge for roof drainage and where it is being directed.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
04/13/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Rene Flores
Wed 4/13/2022 12:46 PM

REVIEW NOTICE
Returned for Corrections: DP21-0229

DESCRIPTION: Site/Grading - New Office Construction. 1001 E SILVERLAKE RD

FEE BALANCE: $ 165.00
(two additional review hours by Fire Dept)

ONLINE PAYMENTS
** If amount doesn't match "Fee Balance", check back in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your THIRD submittal documents accordingly, example: 3_Comment Response Letter

3. UPLOAD A RESUBMITTAL to Filedrop:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents

Thank you.
Sharon Beasley, Certified Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
04/13/2022 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Needs Review