Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP21-0213
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 08/27/2021 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | |
| 08/27/2021 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 08/27/2021 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | |
| 08/31/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | Development Package Comments: Sheet 1 1. Please provide two 3"x 5" boxes for approval stamp and Pima County Addressing 2. The record number for this project is DP21-0213. Please add to all sheets. Sheet 5 3. Provide information for proposed improvements/materials or change shading to distinguish new offsite improvements Sheet 6 4. The trash enclosure detail calls out detail 6, but it is labeled here as detail 7. Please revise 5. Please clarify storm drain keynote 1, plan shows existing RCP. 6. Provide flow-line to basin and evaluate need for protection into basin Sheet 10 7. The ramp details show no elevation difference between pavement and top of curb. Please revise. SWPPP Comments: Sheet 43 1. Identify permanent and temporary SWPPP 2. Please show construction entrance/exit 3. Show limit of disturbance 4. Identify existing topography cover 5. Add arrows to show flow directions Drainage Comments: 1. Figure 2 - Watersheds N3, N4 and N5 are shown on map but Hydrologic Data sheets at end do not correspond to those areas. Please review and revise as necessary. Review and Comments provided by third party engineer reviewers under contract with the City of Tucson. For Questions or Concerns contact: Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 09/01/2021 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Email from: Jay Gomes <jgomes@azdot.gov> To: CDRC Wed 9/1/2021 8:59 AM Approved. No comments on this Development Plan submittal. James Gomes ADOT |
| 09/10/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: The Bridges Sub-Area B-III – Lots 6, 8 & 9 Development Package (1st Review) DP21-0213 TRANSMITTAL DATE: September 10, 2021 DUE DATE: September 17, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is August 18, 2022. CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0213, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 2. COMMENT: 2-06.4.7.A.4 – Remove the Use Specific Standards listed under General Note 3 as they do not apply. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 3. COMMENT: 2-06.4.9.G – For the area of Phase 2 demonstrate what is proposed of dust control. 4. COMMENT: 2-06.4.9.H.5.a – Per PAD-15 Section C.2.3.C.4.i the required parking for retail is “4 spaces for each 1,000 square feet of GFA” not 1 space per 300 sq. ft as listed in the vehicle parking space calculation. 5. COMMENT: 2-06.4.9.H.5.d – Zoning was not able to find the proposed short-term bicycle parking for Building 2, there is no keynote provide and it appears that the rack is covered by keynote 14 shown along the east side of the building. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 09/16/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/16/2021 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | Email from: Howard.Dutt@TucsonAz.gov To: CDRC Thu 9/16/2021 8:18 AM No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks and Recreation, (520) 631-2030 |
| 09/20/2021 | SBEASLE1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approved | View the letter in "Documents" section of PRO: "Tucson Airport Approval Letter, 09.17.21". |
| 09/22/2021 | JPEELDA1 | COT NON-DSD | FIRE | Reqs Change | Fire hydrant shall be located within 600' to the furthest part of each building has the hose lays. Provide documentation that the 1 new hydrant provided meets this requirement. Per the IFC 2018, 912.2.1 FDC shall be located on the street of the building. Fire lines show that the FDC will not be located on the street side. Please make that correction. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 09/22/2021 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | View in "Documents" section of PRO: "TEP Approval letter, 09.20.21", "TEP facilities map, 09.20.21", and "TEP redline page, 09.20.21". |
| 09/24/2021 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, PLA PDSD Landscape/Native Plant Preservation Section PROJECT: The Bridges SubArea B-III, Lots 6,8,9 ACTIVITY NO: DP21-0213 Address: 3450-3460 S Kino Pkwy Zoning: PAD-15 Existing Use: vacant, graded pads Proposed Use: TRANSMITTAL DATE: September 24, 2021 DUE DATE: September 17, 2021 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. 1. UDC 2-10.4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. 2. Please provide landscape calculations for required trees in the parking areas on the landscape plan, Admin. Manual 2-10-4.2.A.2.c and landscape borders, UDC Technical Standards 2-10.4.2.f & g. 3. Identify existing trees in parking lot and provide parking area tree calculations for shared parking areas. 4. UDC 7.6.4.B.1 also says that plants are to be distributed evenly throughout the parking area, please make sure that all parking islands have trees in them and they are planted as close as possible to provide shade over the asphalt. If street border trees are being used for parking area trees, they must be located as close to the asphalt as possible. 5. Provide a dimension for top of wall footer to bottom of top dress. Please revise page number (14, not 13) reference for detail 7. 6. Please label the existing and future rights of way for S Kino Pkwy, E Tucson Marketplace Blvd and S ML King Jr Way, UDC 7.6.4.C.2.a. 7. Per Admin. Manual 2-10-4.2.D, provide reference to civil drawings/details that show bike racks, walkways, and screening/retaining walls on landscape plans. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package YOUR NEXT STEPS: Submit documents to the Filedrop https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" 1) Comment Response Letter (your response to the reviewer's Requires changes comments) 2) Plan Set (or individual sheets) 3) Any other items requested by review staff If you have any questions, please contact me at anne.warner@tucsonaz.gov |
| 09/27/2021 | SBEASLE1 | COT NON-DSD | TRAFFIC | Reqs Change | Email from: David.Stiffey@TucsonAz.gov To: CDRC Mon 9/27/2021 7:53 AM Sheet 5, (at the entry off of Tucson Market Place Blvd.) Please note the curb return radii. Sheet 5, (at the entry off of Tucson Market Place Blvd.) Please correct the Sight Visibility Triangle to 20’ X 185’. |
| 09/27/2021 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Reqs Change | Include a copy of Bridges DRC letter for the retail buildings with the next submittal. |
| 10/04/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: lisa bowers Mon 10/4/2021 11:38 AM Returned for Corrections: DP21-0213 DESCRIPTION: Site/Grading/Swppp - The Bridges Sub-Area B-3, Lots 6,8, and 9. FEES DUE: $ 3,348.92 Please pay at a minimum, the REVIEW category fees. A payment is required before your next submittal. ONLINE PAYMENT If amount doesn't match "Fees Due", check back in a few hours https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave this field blank 4- "Continue" 5- In the Pay column - check the boxes 6- "Continue" REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab and you will see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW INCLUDE IN RESUBMITTAL 1) Comment Response Letter (your response to any Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your SECOND submittal documents according to this example: 2_Comment Response Letter FILEDROP for Resubmittal https://docs.tucsonaz.gov/Forms/tucsonpermitapp - Select "Existing Application" - In the "Permit Number" field, enter the number and, if applicable, any notes for our staff Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) |
| 10/04/2021 | SBEASLE1 | COT NON-DSD | REVIEW | Approved | Email from: Eric.Latto@tucsonaz.gov To: CDRC Mon 10/4/2021 10:56 AM Approved. Eric Latto City of Tucson, Transit/SunTran |