Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP21-0208
Parcel: 11012091A

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0208
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 JPEELDA1 COT NON-DSD FIRE Approved
01/27/2022 SBLOOD1 ENGINEERING REVIEW Approved
01/28/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: A. Randolph
cc: J. Lomas
Fri 1/28/2022 10:48 AM

REVIEW NOTICE
Returned for Corrections: DP21-0208

DESCRIPTION: Site/Grading/Swppp - Palo Verde Behavioral Health. 28-bed addition, upgrades to the drive and utilities. 2695 N CRAYCROFT RD

FEE BALANCE: $ 82.50 (one additional hour review time by Fire Dept)

ONLINE PAYMENT
If amount doesn't match "Fees Due", check back in a few hours
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your THIRD submittal documents according to this example: 3_Comment Response Letter

FILEDROP for your Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff
- Select "PLANS" for documents for quicker downloading of your documents on our end

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
12/10/2021 SBEASLE1 START PLANS SUBMITTED Completed
12/29/2021 SBEASLE1 COT NON-DSD TRAFFIC Reqs Change Email from: David Stiffey
To: CDRC
Tue 12/28/2021 7:44 AM

I looked extensively at these documents and did not see a revised plan set, nor any responses to my previous comments.

1. Sheet C200- New curb returns on plan; radius - 25 ft per COT Technical Manual.
2. Sheet C200- New curb per P.A.G. standard 209
3. Sheet C200- New P.A.G. standard 207- curb access ramps at both north and south sides of entry.
4. Sheet C200- Call-out new sidewalk standard; P.A.G. standard 200.
5. Sheet C200- Provide a detail for Site Detail Note No. 20, "Asphalt Drive Cut Repair."
6. Call out pavement "structural section" of entry on plans.
7. Sheet C200- Wherever one sidewalk perpendicularly ties into another sidewalk, it must meet ADA requirements for a "turn-around." (60" X 60" not to exceed 2% in any direction.)


David Stiffey
City of Tucson
12/29/2021 STEVE SHIELDS ZONING REVIEW Approved
12/30/2021 AWARNER1 LANDSCAPE REVIEW Approved Recommend replacing removed trees with 15 gal. drought-tolerant species