Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP21-0197
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
07/07/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/11/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Circle K – 2555 E Drexel Rd Development Package (2nd Review) DP21-0197 TRANSMITTAL DATE: July 11, 2022 DUE DATE: July 13, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is August 25, 2022. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 1. Until completed Zoning cannot approve the DP.COMMENT: 2-06.4.9.I – The proposed dedication called out under Keynote 44 sheet 2 will need to completed prior to approval of this DP. Provide the recordation information within the keynote. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
07/18/2022 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, PLA PDSD Landscape/Native Plant Preservation Section PROJECT: Circle K ACTIVITY NO: DP21-0197, 2nd Address: 2555 E Drexel Rd Zoning: C-2 Existing Use: Undisturbed Sonoran desert Proposed Use: Retail TRANSMITTAL DATE: July 18, 2022 DUE DATE: July 13, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. 1. Please provide a Native Plant Preservation Plan exemption if there are no projected plants. 2. Relocate trees on the north and south sides of the parking area to maximize shading the asphalt. 3. Engineer - the grading plan shows curb cuts along the southern end of the parking lot, but the water will hit the screen wall, show how water is reaching the landscape. 4. Engineer - First flush cannot be directed to the underground drainage system and should be directed to landscape areas. 5. Engineer - Water harvesting areas should be depressed between 6 and 9 inches and should be shown on the grading plan. 6. Engineer - Grading plan does not match water harvesting plan. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package YOUR NEXT STEPS: Submit documents to the Filedrop https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" 1) Comment Response Letter (your response to the reviewer's Requires changes comments) 2) Plan Set (or individual sheets) 3) Any other items requested by review staff If you have any questions, please contact me at anne.warner@tucsonaz.gov |
08/08/2022 | JPEELDA1 | COT NON-DSD | FIRE | Reqs Change | Building shall be within 400' of a hydrant to the furthest part as the hose lays and or fire sprinklers shall be installed IFC 2018, 507.5.1 Letter from Tucson Water shows existing main but not the fire flow to the new hydrant. Provide detail of new hydrant as the one modeled was a 12" main. Also, provide a letter from Tucson water stating that TFD can pull more than 1,000 GPM from each hydrant. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
08/12/2022 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/24/2022 | DSTIFFE1 | COT NON-DSD | TRAFFIC | Reqs Change | DP21-0197 Comments, 1. This project is going to require a PIA- https://www.tucsonaz.gov/tdot/private-improvement-agreement Call 520-791-5100 for further information. (My apologies, I missed this on the first review.) 2. Sheet C3- (Note: There is plenty of right of way and this intersection is not a HAWK Crossing.) Therefore, please have traffic signal poles and pedestrian push button post installed behind the curb access ramps and not within them. Please refer to P.A.G. standard details T 419 & T 420 for pedestrian push button post details. And P.A.G. standard T 413 for the R-Pole detail. The location of the traffic signal pole and ped push button post that is seen in the P.A.G. standard 207 detail (curb access ramp detail) is there "in the event that a pole needs to land in the ramp." If that is the case, then that it is the standard. The last line of the "Note" in the 207 detail states, "…Placed only when applicable & approved by the jurisdiction's Transportation Engineer." The city of Tucson requires that traffic signal poles and pedestrian push button posts be installed "Behind" or at the back of the curb at the back of the ramp. The 10" distance to press the button can still be accomplished. The only other requirement which you need to consider is that the push buttons cannot be more than 10 Ft from the back of curb, at the center of the curb access ramp. Lastly, if you still want to place the TS pole and ped push button within the confines of the ramp, you'll need approval from the city of Tucson's Transportation Engineer/ Administrator. David Stiffey David.Stiffey@tucsonaz.gov |
08/25/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: Jill Kaiser cc: Beni Rich 08/25/2022 REVIEW NOTICE Returned for Corrections: DP21-0197 Site/Grading/Swppp - Circle K store with six-pump fuel canopy. 2555 E DREXEL RD Fee Balance: $0 (zero) Thank you for the payment. YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your THIRD submittal documents accordingly, example: 3_Comment Response Letter 3. UPLOAD documents to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |