Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP21-0195
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 08/24/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A separate permit is required for the installation of a private sewer collection system, lift-stations, and force mains and will require a review of the system design by the Pima County Department of Environmental Quality. Once the PDEQ review is completed, a building permit will be required prior to beginning construction. Reference Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code. 2. Provide the first floor elevations of the proposed buildings. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018. |
| 08/24/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Littletown and Wilmot Industrial Park – Grading Plan Development Package (1st Review) DP21-0195 TRANSMITTAL DATE: August 24, 2021 DUE DATE: August 25, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is August 01, 2022. 2-06.3.0 FORMAT REQUIREMENTS 1. COMMENT: 2-06.3.12 – An index of all sheets submitted in the set shall be provided on the first sheet. 16 sheets were submitted in this set but only 7 are listed in the index. CONTENT REQUIREMENTS 2. COMMENT: 2-06.4.1 - Provide the email address for the “Owner/Developer” listed on the first sheet. 3. COMMENT: 2-06.4.2.A – The title shall match what is shown on final plat S06-270 and include lot 5. 4. COMMENT: 2-06.4.2.D – The total page numbers shall include all pages submitted in the set. 5. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0195, adjacent to the title block on all sheets. 6. COMMENT: 2-06.4.3 – Provide the tentative/final plat case number, S06-270, adjacent to the title block on all sheets. 7. COMMENT: 2-06.4.4.C – Label the section corners on the location map. 8. COMMENT: Until approved by Engineering review Zoning cannot approve the grading plan. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 08/30/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 09/09/2021 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, PLA PDSD Landscape/Native Plant Preservation Section PROJECT: Littletown/Wilmot Industrial Park, Private Streets ACTIVITY NO: DP21-0195 Address: 6702 S WILMOT RD Zoning: I-2 Existing Use: undisturbed Sonoran Desert Proposed Use: Industrial TRANSMITTAL DATE: September 9, 2021 DUE DATE: August 25, 2021 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. 1. UDC 2-10.4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. 2. Demonstrate how S06-270 landscape and native plant plans are still applicable to this submittal and include these sheets with the next submittal. 3. Please include the Commercial Water Harvesting plans for this development. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package YOUR NEXT STEPS: Submit documents to the Filedrop https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" 1) Comment Response Letter (your response to the reviewer's Requires changes comments) 2) Plan Set (or individual sheets) 3) Any other items requested by review staff If you have any questions, please contact me at anne.warner@tucsonaz.gov |
| 09/10/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. A stormwater pollution protection plan is required for this project. City code requires this to be submitted for review along with the grading plans. Submit SWPPP for review. Include a ADEQ checklist demonstrating completeness of plan. 2. Clarify the extent of work in public Right-of-Way and extent of work in private streets in common area. 3. Comments indicate only streets are proposed for this permit. Clarify that the drainage basins are included in this project. Loren Makus loren.makus@tucsonaz.gov |
| 09/14/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: Brandon Alley Tue 9/14/2021 4:43 PM Returned for Corrections: DP21-0195 DESCRIPTION: Grading - Littletown and Wilmot Industrial Park. Lots 1 thru 4, and 6 thru 24, and Common Areas A,B,C,D,E. 6702 S WILMOT RD FEES DUE: $ 2,550.32 Please pay at a minimum, the REVIEW category fees. A payment is required before your next submittal. ONLINE PAYMENT If amount doesn't match "Fees Due", check back in a few hours https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave this field blank 4- "Continue" 5- In the Pay column - check the boxes 6- "Continue" SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab and you will see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW INCLUDE IN RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments by Zoning, Engineering, Landscape/NPPO) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 09.01.21 FILEDROP for Resubmittal https://docs.tucsonaz.gov/Forms/tucsonpermitapp - Select "Existing Application" - In the "Permit Number" field, enter the number and, if applicable, any notes for our staff Thank you. Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) |