Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP21-0153
Parcel: 14043013D

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0153
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 SBEASLE1 START PLANS SUBMITTED Completed
07/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The finish floor elevation of the hangar (2605.28) is less than 12 inches above the elevation of the next upstream manhole (SSMH-03, 2604.98). Provide a note requiring that a backwater valve be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
07/20/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: ANG-ECF Hanger
Development Package (1st Review)
DP21-0153

TRANSMITTAL DATE: July 20, 2021

DUE DATE: July 19, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 17, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0153, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. COMMENT: 2-06.4.9.H.5.a – Demonstrate on the plan that the proposed accessible vehicle parking spaces meet the requirements of ICC A117.1-2009 Section 502. Per 2018 IBC Chapter 11 Section 1106.5 at least one (1) of the accessible spaces shall be van accessible.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/26/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, PLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: TIA ANG-ECF Hanger
ACTIVITY NO: DP21-0153
Address: 1920 E Aeropark Blvd
Parcel: 140-43-013D
Zoning: I-2
Existing Use: Undisturbed Sonoran Desert, graded areas
Proposed Use: Airplane Hanger

TRANSMITTAL DATE: July 26, 2021
DUE DATE: July 19, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. See end of this letter for next steps.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

2. A Native Plant Preservation Plan is required for this project.
3. The trees in the parking lot are not evenly distributed UDC 7.6.4.B.1.a.1. The point of this UDC section is to provide shade over asphalt area. That intent is not met. As there is excess parking, a suggestion is to delete spaces and provide more shade trees. UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.
4. Please screen back the hatch for d.g. on all sheets for maximum readability.
5. Indicate how hydroseed will be irrigated per UDC 4.2.C.7, please indicate on irrigation plan. Tech Standards Man. 4-01.4.2
6. Include site preparation and plant establishment guarantee in notes for hydroseed areas, Tech Standards Man. 4-01.4.1/4.3
7. Indicate water inlets from parking lot to landscape areas on both landscape and civil paving plans.
8. Add a note that indicates all landscape areas will be depressed a min. 6”, 9” is preferred. Change Recessed Planting Areas to Depressed Planting Areas
9. Modify Recessed Planting Area to show a minimum depth of 6”, change title to verbiage above.
10. Add rain sensors to irrigation details, Tech Standards Man. 4-01.4.2.A.
11. Identify where point of drainage is off roof and where the water is going, UDC Administrative Manual 2-10.4.2.C.6
12. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
07/29/2021 LOREN MAKUS ENGINEERING REVIEW Approved
08/02/2021 JPEELDA1 FIRE REVIEW Approved
08/02/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Jim Wright
Mon 8/2/2021 11:26 AM

Returned for Corrections: DP21-0153

DESCRIPTION: Site/Grading/Swppp - Tucson International Airport. ANG-ECF hangar, in kind replacement.
1920 E AERO PARK BL

FEES DUE: $ 6,303.07 - see image at end of this email
Please pay at a minimum, the REVIEW Fees.
A payment is required before your next submittal.

ONLINE PAYMENT
If amount doesn't match "Fees Due", check back in a few hours after it is updated.
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 07.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

Thank you.

Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov