Permit Number: DP21-0146
Parcel: 14043011A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0146
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2021 SBEASLE1 START PLANS SUBMITTED Completed
07/07/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Martin Reservoir & Booster Station SCADA Upgrade
Development Package (1st Review)
DP21-0146

TRANSMITTAL DATE: May 11, 2021

DUE DATE: May 11, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 10, 2022.


CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.1 – Provide the primary contact name, mailing and email addresses, and phone number of the primary property owner on the plan.

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0146, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. COMMENT: 2-06.4.7.A.1 – General Site Note 1 the existing zoning is not correct and should be I-1.

4. COMMENT: 2-06.4.7.A.4 - General Site Note 3 remove the reference to “R-1” and provide the correct zoning along with the correct Use Specific Standers, 4.9.11.A.1, .2, & .4 and 4.9.13.Q.

5. COMMENT: 2-06.4.7.A.6.a – Remove General Site Note 15 as it is not applicable.

6. COMMENT: 2-06.4.7.A.6.a – Remove the reverence to T20SE______ from the title block area as it is not applicable.

2-06.4.7.A.8 - For development package documents provide:

7. COMMENT: 2-06.4.7.A.8.b – Remove General Site Note 10 as it is not applicable.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

8. COMMENT: 2-06.4.9.H.5.a – Show the required 2 vehicle parking spaces on the plan and demonstrate how dust control is accomplished.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/09/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, PLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Tucson Water Martin Reservoir
ACTIVITY NO: DP21-0146
Address: 990 E Valencia Rd
Parcel: 140-43-011A
Zoning: I-1
Existing Use: Water Reservoir
Proposed Use: Reservoir and Booster Station Upgrade

TRANSMITTAL DATE: July 9, 2021
DUE DATE: July 15, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

2. Add a detail/note to depress landscape areas 6”-9” to collect on-site storm water.

3. Add Landscape/Irrigation Maintenance Schedule per UDC 4.2.A.4

4. Provide documentation from City of Tucson Transportation and Mobility department that supports reducing the width of the landscape buffer as well a permitting more than 5’ of encroachment into the right of way by the landscape border.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

If you have any questions, please contact me at anne.warner@tucsonaz.gov
07/14/2021 JVINCEN1 FIRE REVIEW Approved
07/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/15/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Ryan Stucki
Cc: Charlie Sulik
Thu 7/15/2021 11:45 AM

Returned for Corrections , DP21-0146
DESCRIPTION: SITE - Martin Reservoir and Booster Station SCADA upgrade. 990 E VALENCIA RD

FEES DUE: $ 429.00
Please pay at a minimum, the REVIEW Fees. A payment is required before your next submittal.
ONLINE PAYMENT
If amount isn't correct, check back in a few hours after it is updated.
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 07.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

Thank you.

Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services