Permit Number: DP21-0141
Parcel: 11504602D

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0141
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2021 SBEASLE1 START PLANS SUBMITTED Completed
06/30/2021 MGAYOSS1 DESIGN PROFESSIONAL REVIEW Denied 6/30/2021 - Review by María Gayosso.
No MGD/HPZ application has been filed/approved.
07/06/2021 AWARNER1 LANDSCAPE REVIEW Passed
07/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/08/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Sheet 1
1. Please add labels for existing and proposed on the legend.
2. Please provide Right- of - way width, dimensioned width of curbs, and sidewalks on both streets adjacent to the project.
3. Provide a few spot elevations at the patio that will be elevated.
4. Provide elevations at bottom and top of new stars
5. Identify whether all gates are existing to remain or if they are proposed.
6. Provide a 3" by 5" space on the first sheet for PIMA County Addressing to use.
7. Provide bearing at the curve.
8. Please add a keynote for the existing Gas meter or add to legend.
9. Please add symbol with "GT" to legend or add a keynote.
10. Add symbol with "EB" to legend.

Review and Comments provided by third party engineer reviewers under contract with the City of Tucson. For Questions or Concerns contact:
Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
07/08/2021 SBEASLE1 COT NON-DSD TRAFFIC Approved Email from: David.Stiffey@tucsonaz.gov
To: CDRC
Wed 7/7/2021 12:42 PM

Approved.
No Comments

David Stiffey
City of Tucson
07/12/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Gentle Ben’s Brewery – Patio Expansion
Development Package (1st Review)
DP21-0141

TRANSMITTAL DATE: July 12, 2021

DUE DATE: July 08, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is June 03, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.1 -Provide the email address for the Owner listed on the cover sheet.

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0141, adjacent to the title block on all sheets.

3. COMMENT: 2-06.4.3 – Provide the Main Gate & Historic review case numbers adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

4. COMMENT: 2-06.4.7.A.4 – General Note 3 remove the Use Specific Standards listed as they are not applicable, see UDC Table 4.8-4.

5. COMMENT: 2-06.4.7.A.6.a – Unit the Main Gate & Historic reviews are complete Zoning cannot approved this plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/16/2021 FRANK PODGORSKI HPZ ADVISORY BOARD HPZ ADVISORY BOARD DATE Needs Review This non-contributing property is located within the boundaries of the West University Historic Zone. Any changes require review by the West University Historic Zone Advisory Board and the Tucson Pima County Historical Commission Plans Review Subcommittee. Once submitted for a permit, please complete a Historic application to start the Historic review process.
07/19/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Chuck Meyer
Mon 7/19/2021 4:42 PM

Returned for Corrections , DP21-0141
DESCRIPTION: Site - Gentle Bens Brewery, patio expansions. 865 E UNIVERSITY BL

FEES DUE: total is pending

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 07.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

Thank you.

Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov
08/02/2021 JPEELDA1 COT NON-DSD FIRE Approv-Cond Plans shall show the occupant load of every area. Show the new combined occupant load for the buiding. Plans shall show the egress from each area.
Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
08/02/2021 JPEELDA1 COT NON-DSD FIRE Approv-Cond Make sure that all information is listed on the building plans.