Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP21-0139
Parcel: 13824093E

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0139
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2021 SBEASLE1 START PLANS SUBMITTED Completed
06/16/2021 STEVE SHIELDS ZONING REVIEW Approved
06/17/2021 JPEELDA1 FIRE REVIEW Approved Your building exceeds 30' in height. Aerial access shall be provided. The road shall be 26' wide and 15-30' from the building. The loading area might have been the aerial access. Please how where the aerial access is for the building.
Questions, comments and or concerns:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
06/17/2021 JPEELDA1 FIRE REVIEW Approved I am writing regarding your recent comment on DP21-0139. We were pretty sure about the height of the building, but just had the contractor go out and measure it this morning to make sure. It is 26’ high from grade to the top of the parapet wall. - James McMaurtrie

Building does not require aerial access at that height. changed work flow to approved.
06/18/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Approved Email from: COTDSDPermits
To: Lisa Bowers
Fri 6/18/2021 12:30 PM

PLAN APPROVAL NOTICE
PERMIT/ACTIVITY: DP21-0139

DESCRIPTION: Site - Loading dock at CIS Global.

FEES DUE: $ 264.00
ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
If amount isn't correct, check back in a few hours after data transfers.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click "Continue"
5-Under the Pay column, check the boxes
6- Click "Continue"

NEXT STEPS
Please email the following document(s) to: COTDSDpermits@TucsonAZ.gov
(Disregard the automatic email response that will be sent)
1. City of Tucson Permit - Check-marked and signed. See attached.
2. Payment receipt (if paid in the past 1-2 days). If longer than that, no receipt needed.

After we receive the required documentation, please allow a few days for our staff to stamp the approved plans, upload them to PRO (www.tucsonaz.gov/pro), and send you an email notification. That email will include information regarding the approved stamped plans and required inspections. Thank you.

Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services Dept.
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov