Permit Number: DP21-0138
Parcel: 132131170

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0138
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 SBEASLE1 START PLANS SUBMITTED Completed
08/12/2021 SBLOOD1 ENGINEERING REVIEW Approved 1. See previous comment 2 - Still don't see the address and phone number of the firm who prepared the report. It all should be provided on the cover sheet as per Admin Manual section 2-06.4.1
The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
08/25/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Arby’s – Tucson Marketplace
Development Package (2nd Review)
DP21-0138

TRANSMITTAL DATE: August 25, 2021

DUE DATE: August 30, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 30, 2022.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.8 - For development package documents provide:

1. There is still an error on the tracking table, under the ‘ACCESSIBLE PARKING PROR APPROVED DEVELOPMENT” DP16-0094 POPEYES SPACES PROVIDED should be 2 with the total being 116. COMMENT: 2-06.4.7.A.8.d – Bridges Tracking Tables – until comment 4 above is addressed Zoning cannot verify several of the tracking table requirements. Currently there appears to be errors under several categories within the table: Accessible Parking Provided, FLOOR AREA RATIO (FAR) - OVERALL TUCSON MARKETPLACE PROJECT TOTALS TO DATE, PRIOR APPROVED DEVELOPMENT TOTALS TO DATE. Add the entire DP case number to OPEN SPACE REQUIREMENTS - SUB AREA "A" for this project.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2. His comment was not addressed correctly. The 1’-0” setback requirement is at the drive-through window. COMMENT: 2-06.4.9.H.5 – Show the required 1’-0” setback from the building to the drive-through lane, see UDC Article 7.4.6.F.2.a.(2).

3. This comment was not fully addressed, there are not dimensions shown for the stacking spcaes. COMMENT: 2-06.4.9.H.5 – Show and dimension the required stacking spaces on the plan, see UDC Article 7.4.7.

4. This comment was not addressed. Per ICC A117.1-2009 Section 502.4.1 “Van parking spaces that rea angled shall have the access aisles located on the passenger side of the parking space. COMMENT: 2-06.4.9.H.5.a – The proposed van accessible parking space does not meet the requirements of ICC A117.1-2009 Section 502.4.1.

5. This comment was not addressed, UDC Articles 7.4.9.B.1.e, 7.4.9.B.2.f were not addressed. COMMENT: 2-06.4.9.H.5.d – Provide a fully dimensioned short – term bicycle parking space detail that demonstrates how the requirements of UDC Articles 7.4.9.B.1, .2.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/25/2021 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved Letter:

August 23, 2021

RE: DP21-0138 Site/Grading - Arby's - Tucson Marketplace. New restaurant, 2nd submittal, Received August 4, 2021

Thank you for the opportunity to comment on DP21-0138 Arby’s, new restaurant, Tucson Marketplace; 2nd Submittal, a development package application for a 0.85 acre site, which is located southeast of the intersection of East Tucson Marketplace Boulevard and South Park Avenue. The property is zoned Planned Area Development 15 (PAD-15) and the project would support the development of a commercial restaurant.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority is satisfied with the 2nd submittal of this project and has no additional comments to provide.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux, C.M., Senior Airport Planner
08/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Installing a backwater valve upstream of a grease interceptor can result in frequent fouling issues in normal operation and contamination of the grease interceptor in the event of a backwater event. Reference: Section 1003.3.5, IPC 2018. [Initial comment: Show the location (or locations) of the 4-inch backwater valve described in sewer keynotes #1, Page 6 of 8. Reference: Section 107.2.1, IBC 2018.]
08/31/2021 SBEASLE1 COT NON-DSD TRAFFIC Approved Email from: David Stiffey
To: CDRC
Tue 8/31/2021 2:29 PM

Approved. No further comments.

David Stiffey
City of Tucson
08/31/2021 JPEELDA1 COT NON-DSD FIRE Reqs Change Please show the distance from the closest hydrant to the furthest part of the building as the hose lays.
Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
09/06/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Richard Macias
Mon 9/6/2021 2:39 PM

Returned for Corrections: DP21-0138
DESCRIPTION: Site/Grading - Arby's - Tucson Marketplace. New restaurant. 1050 E TUCSON MARKETPLACE BL

Fee Balance: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 3rd submittal documents according to this example: 3_Comment Response Letter, 09.01.21

FILEDROP for Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff


Thank you.
Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
09/06/2021 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved Email from: Peter McLaughlin
To: CDRC
Cc: John Beall
Mon 9/6/2021 2:06 PM

Approved.

Peter McLaughlin
City of Tucson
(Outlook for iOS)