Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: DP21-0123
Parcel: 113071050

Review Status: Completed

Review Details: GRADING

Permit Number - DP21-0123
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2021 SSHIELD1 NPPO REVIEW Passed
06/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 1620 E Hedrick – Lots 1-3
Grading Plan (1st Review)
DP21-0123

TRANSMITTAL DATE: June 9, 2021

DUE DATE: June 10, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. Zoning has reviewed the grading plan for compliance with DP20-0163 and although the grading plan appears to match the tentative plat zoning cannot approve the grading plan until the tentative plat are approved and all other Zoning comments have been addressed.

2. 2-06.4.3 - Provide the grading plan case number, DP21-0123, adjacent to the title block on all sheets.

3. Zoning cannot approve the grading plan until approved by Engineering and Landscape.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
06/22/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Development Package DP20-0163 must be approved and issued before this grading Development Package DP21-0123 can be approved.
2. Show drainage patterns including roof drainage for the site. Include sufficient grade information to substantiate the drainage patterns.
3. Show pedestrian path surface for route from vehicle use areas to entries to residential units.
4. Show access locations to fenced areas of yards.
5. Show barriers at property lines to prevent vehicle from overhanging or inadvertently driving onto adjacent parcel.

Loren Makus, EIT
loren.makus@tucsonaz.gov
06/22/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Jeff Stanley
Tue 6/22/2021 2:26 PM

Returned for Corrections Notice
PERMIT/ACTIVITY: DP21-0123

DESCRIPTION: Grading/Floodplain - 1620 E. Hedrick Drive, Lots 1,2,3.

(The related Floodplain Use Permit # T21ot00436 has been issued and fees are paid.)

FEES DUE: $ 573.10
Please pay at a minimum, the REVIEW Fees. A payment is required before your next submittal. Thank you.
ONLINE PAYMENT
If amount isn't correct, check back in a few hours after it is updated.
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click "Continue"
5- Pay column - check the boxes
6- Click "Continue"

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter the permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW


Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov