Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP21-0117
Parcel: 117050180

Address:
412 N 4TH AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0117
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2021 SBEASLE1 START PLANS SUBMITTED Completed
05/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The rim elevation of the next upstream manhole (3004-68) is 2382.36’; where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
05/20/2021 JPEELDA1 FIRE REVIEW Reqs Change Note 32 on sheet 3 of 11 shows where the fire riser will be located. Code requires that the FDC shall be located on the street side of the building. Add note to drawings so that the contractor knows. Please show the existing fire hydrants on your plans.
06/07/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination

FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: DP21-0117
Address: 412 N 4th Ave (et.al), Food Conspiracy Co-op Expansion
Parcel: 117-05-0180,-0240, -0210,-0200,-0220
Zoning: C-3, Downtown Links Overlay District
Existing Use: Food and Beverage Sales, office uses
Proposed Use: Parking, expansion of ex. bldg. and new storage structure

TRANSMITTAL DATE: June 7, 2021
DUE DATE: June 9, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section 5.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

2. Please ensure that all related case numbers and this DP number are on all plans.

3. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

4. The landscape requirements are subject to the Downtown Links Overlay District, which has specific requirements for the 3rd Avenue streetscape. Show/describe how plan meets these requirements.

5. A Commercial Water Harvesting Plan is required in accordance with UDC Technical Standards Manual – Section 4-01.0.0. Commercial Rainwater Harvesting and Section 5-01.0.0 Landscaping and Screening

6. Show point of drainage off roof areas, amount of flow, and disposition of flow.

7. Please clearly label the curb inlets to landscape areas (WHIA) to allow water into the planted areas. Grading/paving plan should match landscape plans.

8. Provide a detail to show tree planting with root barrier adjacent to walkways.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

If you have any questions, please contact me at anne.warner@tucsonaz.gov
06/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Food Conspiracy Expansion
Development Package (1st Review)
DP21-0117

TRANSMITTAL DATE: June 8, 2021

DUE DATE: June 9, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 10, 2021.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0117, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.6.a – General Note 22 remove the reference to “UDC SEC. 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R) as 4th is not an MS&R in this location.

3. COMMENT: 2-06.4.7.A.6.a – Based on General Note 22 it appears that you will be using the IID process. Provide the IID case number adjacent to the title block on all sheets and provide a general note that states the case number, date of approval, what was modified and list any conditions of approval. If you are not going to use the IID remove General Note 22 from the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. COMMENT: 2-06.4.9.E – As the west portion of the site is made up of two parcels and the east portion is made up of three parcels a lot combination is required. Provide a copy of the approved Pima County Combo request form with you next submittal.
5. COMMENT: 2-06.4.9.H.5.a – The vehicle parking space calculation is not correct. This site is not located within the Downtown Parking District. Revise the calculation.

6. COMMENT: 2-06.4.9.H.5.a – Detail “A sheet 6 the mounting height of the accessible sign is not correct. Per ParkWise when located within a pedestrian way the bottom of sign should be 74” above finish grade.

7. COMMENT: 2-06.4.9.H.5.d – Per UDC Article 7.4.9.B.2.g a bicycle rack must be a minimum of two- and one-half feet from a wall or other obstruction. That said on the “BIKE RACK SPACEING” Sheet 3 the two groups of short-term bicycle racks both appear to have some type of obstruction near the west end. Provide a dimension.

8. COMMENT: 2-06.4.9.O – It appears that you are using established area setbacks for the street setbacks per UDC Article 6.4.5.C.1 .b Where a lot abuts more than one street, the owner chooses which street lot line is the front lot line. From other than the front lot line, the street perimeter yard is ten feet. That said as both sites have existing structure that do not meet either street setback, and it doesn’t appear that any new structures encroach into a street perimeter yard setback, it is your choice as to which is the front street of side street for street perimeter yard setbacks.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/17/2021 LOREN MAKUS ENGINEERING REVIEW Needs Review 1. Comments from zoning and landscape reviewers may require changes to the plans. The changes will be reviewed on the next submittal.
06/18/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Lisa Bowers
Fri 6/18/2021 11:03 AM

Returned for Corrections Notice
PERMIT/ACTIVITY: DP21-0117

DESCRIPTION: Site/Grading - Food Conspiracy expansion.

FEES DUE: $ 1,796.10
Please pay at a minimum, the REVIEW Fees. A payment is required before your next submittal. Thank you.

ONLINE PAYMENT
If amount isn't correct, check back in a few hours after it is updated.
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click "Continue"
5- Pay column - check the boxes
6- Click "Continue"

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter the permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW


Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov