Permit Number: DP21-0114
Parcel: 125073260

Address:
420 N OLSEN AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0114
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2021 SBEASLE1 START PLANS SUBMITTED Completed
05/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location and size of water lines, water meters, and fire hydrants.
b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The points of connection to existing public sewers.
d. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
05/17/2021 JPEELDA1 FIRE REVIEW Approved
06/02/2021 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

Email sent from: Robin Freiman <Addressing@pima.gov>
To: CDRC
Wed 6/2/2021 9:54 AM

Midtown Casitas, DP21-0114, 1st submittal review is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
06/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Midtown Casitas – Studio & Laundry Addition
Development Package (1st Review)
DP21-0114

TRANSMITTAL DATE: May 11, 2021

DUE DATE: May 11, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 04, 2021.

1. This site is considered nonconforming for vehicle use area landscaping. The proposed studio expansion increases the intensity of the site by adding an additional bedroom, see bedroom definition UDC Article 11.4.3. As this is considered and expansion of a nonconforming site the site loses the nonconforming status and must be modified to meet current UDC standards such as vehicle use area, landscape, pedestrian circulation etc.

2-06.3.0 FORMAT REQUIREMENTS

2. COMMENT: 2-06.3.7 – Remove the aerial photo from the location map.

CONTENT REQUIREMENTS

3. COMMENT: 2-06.4.1 – Provide an email address for the owner.

4. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0114, adjacent to the title block on all sheets.

5. COMMENT: 2-06.4.4.B - Identify all streets that abut the subject property on the location map.

6. COMMENT: 2-06.4.4.C – Label the sections corners on the location map.

2-06.4.7 - General Note The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

7. COMMENT: 2-06.4.7.A.4 – The use listed under General Note 4, residential, is not correct and should be listed as Multifamily subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

2-06.4.7.A.8 - For development package documents provide:

8. COMMENT: 2-06.4.7.A.8.a – Provide the floor area for each building on the plan.

9. COMMENT: 2-06.4.7.A.8.b – Provide a lot coverage calculation on the plan that meets the requirements of UDC Article 6.4.3.

10. COMMENT: 2-06.4.7.A.8.c – Provide a building area expansion calculation on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

11. COMMENT: 2-06.4.9.F – General Note 2 is not correct. The adjacent parcels to the east and south are zoned R-1.

12. COMMENT: 2-06.4.9.H.5 – The vehicle use area will need to be brought up to current UDC standards, see UDC Article 7.4 to include but not limited to number of required vehicle parking spaces, standard & accessible, access to the site, vehicle maneuvering into & out of vehicle parking spaces, surfacing requirements etc.

13. COMMENT: 2-06.4.9.H.5.a – Provide a vehicle parking space calculation on the plan. This calculation shall include the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. See UDC TABLE 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED, RESIDENTIAL USE GROUP, Multifamily Dwellings - 0-70 units/acre for required parking.

14. COMMENT: 2-06.4.9.H.5.d – Provide a calculation for short- and long-term bicycle spaces required and provided. Also provide a short- & long-term bicycle parking detail that demonstrates how the requirements of UDC Articles 7.4.9.B .C & .D are met.

15. COMMENT: 2-06.4.9.O – Until the building heights are provided, see comment 18, perimeter yard setback requirements cannot be verified.

16. COMMENT: 2-06.4.9.O – The street 10’-0” setback is not correct. Per UDC Article 6.4.5.C.1 the street perimeter yard setback is 20’ or 1-1/2 the height of the exterior wall, greater of the two. Remove the setback line and provide setback dimensions.

17. COMMENT: 2-06.4.9.O – Per UDC Article 6.3.3.C Multifamily development is considered a nonresidential use. Per UDC Article 11.3.7.3 Multifamily development is defined as any residential development consisting of three or more dwelling units on an integrated site or single lot. That all said per UDC Table 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-2 Zone, nonresidential use to a residential zone the required perimeter yard setback is 10’ or ¾ the height of the exterior, greater of the two. This setback applies to the north, south and east property lines.

18. COMMENT: 2-06.4.9.Q – Provide the square footage, height and specific use proposed within the footprint of the building(s).
19. COMMENT: 2-06.4.9.R – Provide width dimensions for all existing and proposed sidewalks on site, Per TSM Section 7-01.4.3.A the minimum width is 4’-0”.

20. The development package shall be submitted as a multi-page pdf file.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/10/2021 AWARNER1 LANDSCAPE REVIEW Approved
06/15/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Note that the lowest floor of the new structure must be one foot higher than the base flood elevation as shown on the elevation certificate.

10. Sign the application and submit.

11. Add a note to the development package and to the building plans indicating the Base Flood Elevation is 2440.9 FT NAVD 88 and the finished floor elevation must be 2441.9 FT NAVD 88 or higher.
06/16/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: MidtownCasitas
Wed 6/16/2021 10:08 AM

Returned for Corrections Notice
PERMIT/ACTIVITY: DP21-0114

DESCRIPTION: SITE - Midtown Casitas. Addition of laundry room and studio to existing triplex building. 420 N OLSEN AV

FEE BALANCE: $0 (zero) Thank you for the payment.

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter the permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW


Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov