Permit Review Detail
Review Status: Completed
Review Details: TENTATIVE PLAT REVIEW
Permit Number - DP21-0102
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 08/17/2021 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | Email from: TEP-DEVREV <TEPDEVREV@tep.com> To: CDRC Mon 8/16/2021 5:18 PM Easements for TEP facilities must be shown on the final plat before TEP will approve the plat. Land specific requirements to follow. Should you have any easement questions, please contact Courtney Tejeda in our Land Resources department at (520) 820-9154. Tucson Electric Power Co. Land Resources Department CTejeda@TEP.com |
| 08/17/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The current FFE for lot 11 (2874.49’) is more than 12-inches above the rim elevation of manhole #3 (2873.37’) and does not require a backwater valve. [Initial comment: The rim elevation of new sanitary manhole #3 (2873.37’) is less than 12” below the first-floor elevation of lots 10 (2874.05’) and 11 (2874.32’). Provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 08/17/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/18/2021 | SBEASLE1 | PIMA COUNTY | ADDRESSING | Approved | Email from: <Addressing@pima.gov> To: CDRC Wed 8/18/2021 11:14 AM Saguaro Trails, 2nd Submittal, DP21-0102 is Approved by Pima County Addressing. Thank you, Robin Freiman, Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 08/27/2021 | AWARNER1 | LANDSCAPE | REVIEW | Approved | |
| 09/03/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 09/06/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: Ryan Stucki Mon 9/6/2021 1:44 PM Returned for Corrections: DP21-0102 DESCRIPTION: Tentative Plat: Saguaro Trails, 10090 E DREXEL RD Fee Balance: $0 (zero) Thank you for the payment. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab and you will see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW INCLUDE IN YOUR RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your 3rd submittal documents according to this example: 3_Comment Response Letter, 09.01.21 FILEDROP for Resubmittal https://docs.tucsonaz.gov/Forms/tucsonpermitapp - Select "Existing Application" - In the "Permit Number" field, enter the number and, if applicable, any notes for our staff Thank you. Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) |