Permit Number - DP21-0086
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 04/12/2021 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 04/12/2021 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | |
| 04/12/2021 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | |
| 04/14/2021 | SBEASLE1 | PIMA COUNTY | ADDRESSING | Passed | 04/14/21 Pima County Addressing does not need to perform any review. Thank you Nicholas Jordan, Addressing Specialist Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701, (520) 724-9623 |
| 04/14/2021 | JVINCEN1 | COT NON-DSD | FIRE | Approved | |
| 04/27/2021 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | (The TEP FACILITIES MAP and TEP REDLINE PAGE can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.) April 27 2021 SUBJECT: Craycroft Office, DP21-0086 Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted April 12, 2021. There do not appear to be any conflicts. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Ms. Bianca Maubach New Business Project Manager P. O. Box 711 (OH 204) Tucson, AZ 85702 520-307-3864 Should you have any technical questions, please contact the area Designer Martin Rodriguez, at (520) 991-5495 Sincerely, Conor Mahoney, Office Support Assistant TEP, Design/Build |
| 04/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site drawing to include the following existing utility information: a. The location fire hydrants. b. The location and size of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number. c. The points of connection to existing public sewers. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018. |
| 04/29/2021 | AWARNER1 | ZONING | REVIEW | Reqs Change | CDRC PDSD Zoning Review FROM: Anne Warner, RLA, Planner PROJECT: Craycroft Office, DP21-0086 Address: 1834 E Craycroft Rd Parcel: 121-02-1910 Zoning: O-1 Proposed Use: Office TRANSMITTAL DATE: April 29, 2021 COMMENTS: 1. Development must comply with the Administrative Manual Section 2-06 - Development Package. 2. Proposed use is allowed in the O-1 zone, add as a General Note on the Development Package; allowed under the Commercial Land Use Group, Professional and Administration Office UDC 4.8.6, subject to Use Specific Standards 4.9.13.O. 3. Minimum lot size for the O-1 zone is 10,000 sf, not 0’, and the maximum height is 16’, not 75’, as noted for I-1 zone in the Site Notes (#4 & 24, 25.) 4. Required parking is calculated using the Commercial Services Land Use Group, 1 parking space/300 sq.ft GFA. 5. Both the DP and building plans can be submitted at any time, however the DP must be approved prior to the building plans approval. 6. Parking space dimensions conflict with details. 7. Include dedication information on all easements traversing the property. 8. All rezoning conditions need to met and clearly delineated in the Development Package, add General Note for rezoning case number C9-19-20. 9. Location map shows two parcels rather than one that is being reviewed in this development package. If you have any questions, please contact me at anne.warner@tucsonaz.gov or (520) 837-4969. |
| 04/29/2021 | AWARNER1 | ZONING | REVIEW | Reqs Change | CDRC PDSD Zoning Review FROM: Anne Warner, RLA, Planner PROJECT: Craycroft Office, DP21-0086 Address: 1834 E Craycroft Rd Parcel: 121-02-1910 Zoning: O-1 Proposed Use: Office TRANSMITTAL DATE: April 29, 2021 COMMENTS: 1. Development must comply with the Administrative Manual Section 2-06 - Development Package. 2. Proposed use is allowed in the O-1 zone, add as a General Note on the Development Package; allowed under the Commercial Land Use Group, Professional and Administration Office UDC 4.8.6, subject to Use Specific Standards 4.9.13.O. 3. Minimum lot size for the O-1 zone is 10,000 sf, not 0’, and the maximum height is 16’, not 75’, as noted for I-1 zone in the Site Notes (#4 & 24, 25.) 4. Required parking is calculated using the Commercial Services Land Use Group, 1 parking space/300 sq.ft GFA. 5. Both the DP and building plans can be submitted at any time, however the DP must be approved prior to the building plans approval. 6. Consider changing Acacia greggi to a plant that will scratch paint or snag clothes. Replace the word “natural” with “native” for clarity. 7. Include dedication information on all easements traversing the property. 8. All rezoning conditions need to met and clearly delineated in the Development Package, add General Note for rezoning case number C9-19-20. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards. If you have any questions, please contact me at anne.warner@tucsonaz.gov or (520) 837-4969. |
| 05/03/2021 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | Email received from: Howard Dutt To: CDRC Mon 5/3/2021 11:19 AM No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA, Landscape Architect Tucson Parks and Recreation (520) 837-8040 |
| 05/14/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/19/2021 | SBEASLE1 | COT NON-DSD | TRAFFIC | Reqs Change | Email from: David.Stiffey@TucsonAz.gov To: CDRC Wed 5/19/2021 3:00 PM DP21-0086 Traffic Review Comments: 1. Keynote 4, on sheet C2, states "extruded curb" -curb returns coming into the property off of Craycroft Rd. Curbing within the right of way must be according to P.A.G. Standard 209. And cannot be extruded according to Development Standard 3-01.3.2.B.1.2 2. Due to the limited property frontage from Craycroft Rd. please update the entrance to P.A.G. Standard 206; Driveway Apron. (This is the modified 206 according to the "solid-circle note" on sheet 1 of 2- P.A.G. 206. 3. Tie-in to existing sidewalk north of property entrance according to P.A.G. Standard 203 4. Show spot grades of ADA compliance where sidewalk will meet new P.A.G. standard 206 driveway apron. 5. Trash and Recycle receptacles need to be moved out of the right of way and on to the property per COT-Technical Standard, Section 8; All Development, 8-01.5.4 6. On Sheet C2, where Keynote 8 (4 Ft. wide raised concrete sidewalk) will intersect new sidewalk in the ROW, show spot grades that are in ADA compliance. 7. "Sight Visibility Triangles" need to be corrected. The hypotenuse of the triangle begins on the intersecting road (or property in this case) of the stem side of the triangle. According to COT Development Standard, 3-01.5 and figure 16 8. Due to Craycroft Rd. being an MS&R street, show "future" sight visibility triangle according to COT Development Standard, 3-01.5.1.B.2 9. Keynote 6 states "stop sign." There isn’t a keynote 6 on plan sheet C2. Please update. David Stiffey Program Coordinator City of Tucson Transportation and Mobility |
| 05/24/2021 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Passed | Email from: From: John Beall <John.Beall@tucsonaz.gov> Sent: Monday, May 24, 2021 9:21 AM To: COTDSD Please close out the Entitlement review folder as Pass. Thank you. |
| 06/01/2021 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, RLA PDSD Landscape/Native Plant Preservation Section PROJECT: DP21-0086 Address: 1834 N. Craycroft Rd. Parcel: 121-02-1910 Zoning: O-1 Existing Use: Residential home Proposed Use: Office, parking TRANSMITTAL DATE: June 1, 2021 DUE DATE: May 5, 2021 COMMENTS: 1. UDC 2-10.4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. 2. Please ensure that all related case numbers, specifically the rezoning case, and this DP number are on all plans. 3. 4. Under General Notes on sheet 1, #24, list required setbacks for R-1 properties, 5. Note #25 is in conflict with plant notes, 5' or 10' masonry wall? Max. allowed height is not 75'. 6. Note #17 is incorrect, there are no shrubs provided. 7. Notes #7, 8 and 17 are in conflict, please revise. 8. A 10' landscape border is required adjacent Craycroft Rd. Please label and dimension Please label and dimension landscape border widths AM Section 2-10-4.2.A.2.f. & .g, for all required borders (north, east, and west) and walls (north, east). The street landscape border must provide 50% vegatative cover within the border, provide calculations. 9. On the plant legend, please remove plant materials not used for this project. 10. Differentiate between the existing and proposed walls on landscape plan. 11. Backflow preventer detail is required. 12. Irrigation Notes #4, revise to say irrigation plan is schematic. 13. Irrigation Notes #20 is in conflict with sleeves shown on the plan 14. Water harvesting plan is missing, please submit. 15. Indicate on plant legend that single trunk mesquites will be provided in the parking areas per 5-01.3.3.C. Only trees with single trunks may be planted within these planters because trees with multiple trunks need wider areas of growth and may interfere with the parked vehicles. 16. Add plant and irrigation maintenance schedule to plans, per UDC Administrative Manual 2-10-4.4. a. Pruning schedules to show that plant material will maintain pedestrian and vehicular clearances or that the material will establish opaque hedge screens, if required; b. Replacement criteria, should plant material not survive; (already on plan) c. Replacement or upkeep maintenance schedules for inert ground cover materials; d. Upkeep maintenance schedules for exterior hardscape materials; and, e. Maintenance and replacement schedules for irrigation systems. 17. Show point of drainage off roof areas, amount of flow, and disposition of flow. 18. According to parking calculations 21 trees are required, but 15 trees are provided in the new parking area, please add 6 trees to the parking area. The trees in the area north of the parking lot will not count towards this requirement. 19. Provide a detail to show tree planting with root barrier adjacent to walkways. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package If you have any questions, please contact me at anne.warner@tucsonaz.gov or (520) 837-4969. |
| 06/02/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email sent from: COTDSDPermits To: RM Mon 6/7/2021 1:44 PM Returned for Corrections Notice PERMIT/ACTIVITY: DP21-0086 DESCRIPTION: SITE/GRADING: Craycroft office. 1834 N CRAYCROFT RD FEE BALANCE: pending INCLUDE IN YOUR RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21 FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then enter the permit number) SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on REVIEW DETAILS - Documents - click on VIEW Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs:COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) Email for Building Permits: PDSDinquiries@TucsonAz.gov |