Permit Number: DP21-0075
Parcel: 13418113B

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP21-0075
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2021 SBEASLE1 START PLANS SUBMITTED Completed
03/30/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Devereux Advanced Behavioral Health – Perimeter yard fence
Development Package (OK to Submit
DP21-0075

TRANSMITTAL DATE: March 30, 2021


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is March 25, 2022.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.5 – Remove the two Building Code approval stamps from the plan and provide an area for the Development Package approval stamp in the lower right quadrant for this stamp.

2. COMMENT: 2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet. This map shall cover approximately one square mile, be drawn at a minimum scale of three-inch equals one mile, and provide the following information; a. Show the subject property approximately centered within the one square mile area. Identify major streets within the square mile area and all streets that abut the subject property.

CONTENT REQUIREMENTS

3. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0075, adjacent to the title block on all sheets.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

4. COMMENT: 2-06.4.8.A - Provide site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet, to hundredths of a foot, or other functional reference system.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

5. COMMENT: 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

6. 2-06.4.9.H.5 - Clearly show the proposed fence on the development package and indicate the height. Per UDC Article 7.4.6.F.2.b Access lanes and PAALs must be setback at least two feet from a wall, screen, or other obstruction over six inches, and per UDC Article 7.4.6.D.2.b A motor vehicle off-street parking space must have a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height.

7. COMMENT: 2-06.4.9.X – Clearly show the proposed fence on the development package and indicate the height. If the fence exceeds 6’-0” along the south or west property line and does not meet perimeter yard setbacks a Design Development Option (DDO) may be required for fence height within a perimeter yard setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf.

If you have any questions about this transmittal, please contact Steve Shields @ Steve.Shields@tucsonaz.gov. My email will return an automatic response stating that I have retired but I am currently working as a contract employee and will respond to your questions regarding this review.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/30/2021 LOREN MAKUS ENGINEERING REVIEW Passed
03/30/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Passed