Permit Number: DP21-0067
Parcel: 14125005B

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0067
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2022 SBEASLE1 START PLANS SUBMITTED Completed
02/07/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/16/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Approved Email from: <Addressing@pima.gov>
To: CDRC
cc: Erin Harris
Tue 2/15/2022 3:30 PM

Pima County Addressing approves DP21-0067, Voyager Mobile Home Park, 2nd Submittal.
Thank you
Nicholas Jordan, Addressing Specialist

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701, (520) 724-9623
02/17/2022 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change (The comment letter mentioned below can be viewed as a PDF. See the "Documents" section of PRO: "TAA review comments, second submittal, 02.15.22")

Email from: Scott Robidoux <srobidoux@flytucson.com>
To: CDRC
Tue 2/15/2022 7:00 PM

Attached is a copy of my comment letter on DP21-0067. I am unable to approve the 2nd submittal of this project. I have included the text I need revised on the development package so I can approve this project. I have also included the applicant on this email so they can receive a copy of my comment letter.
Thank you,

Scott Robidoux, C.M., Manager of Planning

TUCSON AIRPORT AUTHORITY
7250 South Tucson Boulevard, Suite 300
Tucson, AZ 85756
Phone 520-573-8100, Direct 520-573-4811
02/28/2022 STEVE SHIELDS ZONING REVIEW Approved
03/01/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet 10 shows Driveway E to the north in excess of 150' without a turnaround provided compliant with IFC 2018, Appendix D.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
04/04/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination

FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Ordinance Review Section

PROJECT: DP21-0067, 2nd submittal
Address: 7500 E Voyager Road
Zoning: MH-2
Existing Use: Undisturbed Sonoran Desert
Proposed Use: Mobile Home Subdivision

TRANSMITTAL DATE: April 4, 2022
DUE DATE: February 15, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape/NPPO Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the Unified Development Code (UDC) Administrative Manual (AM) Section 2-11, City of Tucson Uniform Development Code (UDC) Article 7.7 Native Plant Preservation, 7.6 Landscaping and Screening, and the UDC Technical Standards Manual (TSM).
The required Environmental Resource Report has been reviewed and accepted.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

2. On Sheet 1, F- Trails it states that there are no Pima County Trails adjacent to the site, however, the rezoning conditions state that the North Fork of Airport Wash is listed on the Regional Trail System Master Plan. Please elaborate. Also, please include the 8’-wide trail adjacent to the North Fork on the NPP plans. The trail should meander to avoid significant vegetation.
3. The Environmental Resource Report submitted is for the rezoning, which is not sufficient in detail for a development plan. A detailed ERR is required to address impacts, Protected Riparian Areas, and mitigation to the North Fork of the Airport Wash. Please note that only crossings, not encroachment are allowed in ERZ washes. UDC 4-02.2.B.2
4. Please provide all NPP mitigation worksheets (can be submitted as a separate document) and an explanation regarding the low viability of the trees.

If you have any questions, please contact me at anne.warner@tucsonaz.gov or (520) 837-4969.
04/06/2022 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. The street/PAAL has been modified to remove the knuckles at corners. Demonstrate adequate maneuverability for fire apparatus and solid waste service vehicles.
2. Pad grades for lots 10, 11, 224 and 225 are at or below the BFE for the adjacent floodplain. Increase the proposed pad grades so the parcels will not be subject to flooding.
3. Other pads adjacent to the floodplain have minimal freeboard compared to the BFE. Ensure enough margins of safety are provided.
4. The SWPPP identifies the outfall to an unnamed wash. Clarify the Airport Wash is the receiving water.
5. Grading is shown into the floodplain of the washes on the site. It is not clear that riparian resources in these areas have been inventoried and identified. Provide an inventory for the disturbed floodplain areas meeting the ERR standard as outlined in the riparian protection technical standard.

Loren Makus
loren.makus@tucsonaz.gov
04/07/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Erin Harris
Thu 4/7/2022 12:17 PM

REVIEW NOTICE
Returned for Corrections: DP21-0067

DESCRIPTION: Site/Grading/Swppp/Floodplain - Voyager Mobile Home Park. Phases One and Two. 7500 E VOYAGER RD

FEE BALANCE: $ 82.50
(one additional review hour by Fire Dept)

ONLINE PAYMENTS
If amount doesn't match "Fees Due", check back in a few hours
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your THIRD submittal documents accordingly, example: 3_Comment Response Letter

3. UPLOAD A RESUBMITTAL to Filedrop:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents

Thank you.
Sharon Beasley, Certified Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov