Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2021 SBEASLE1 START PLANS SUBMITTED Completed
03/18/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
03/18/2021 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
03/18/2021 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
03/22/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Development Package Comments:
Sheet 1
1. Please provide basis of Bearing and Elevation according to Administrative Manual (AM) Section 2-06.4.8.
2. Please provide name and contact information of firm or individual who prepared the geotechnical report.
3. Site Map: Please provide adjacent property parcel numbers on all sheets and this site's parcel number on cover sheet.
Sheet 2
1. DEVELOPMENT PACKAGE NOTES: Please provide Street and Roads Notes per Administrative Manual (AM) Section 2-06.4.7.
2. DEVELOPMENT PACKAGE NOTES #11: Please also provide areas in acres.
Sheet 3
1. For all sheets: Contour interval should be provided in north arrow and scale block.
Sheet 4
1. For all sheets: Please provide existing Perimeter information (bearing, distance).
2. For all sheets: AM 2-06.4.8 - Please label significant conditions (existing fences, structures etc.) as "To Be Removed" or "To Be Retained" (Typ.)
3. Please add site lighting symbol to legend.
4. Please label Basin
Sheet 6
1. Please label Basin
Sheet 8
1. Please clarify the details of the storm drain pipe at the entrance (such as proposed/existing pipe or ditch, size, and reference sheet number or detail).
2. Add Distance: Please Specify distance between entrance gate and entrance site boundary.
Sheet 10
1. Please label proposed or existing water pipe and other utilities.
2. Please label Proposed Primary Disposal Field, and reference sheet number.
3. Please label Low Point, High Point, direction surface flow and slope (There is a LP at southwest of proposed building: 44.63AC is a LP between 44.69AC and 44.69AC). Will there be water ponding?
4. Please label sewer septic tank and add symbol to legend.
5. Please label slope (west side of parking, slope down to the primary disposal field).
6. Please add fence symbol to legend.
7. Please label drainage slope (east side of the building) and provide detail/information to verify how flowline will be maintained in millings section.
Sheet 11
1. From sheet C301 to sheet C303, earthen/unlined drainage channel: Per Standard Manual For Drainage Design & FloodPlain Management in Tucson, AZ (Rev. July 1998), section 8.5.8 - Channel Slope: It recommend to have minimum slope of 0.3% for unlined channel. The east side of parking lot earthen channel shows design drainage slope of 0.25%, will sediment build up in channel? How the channel will be maintained?
Sheet 12
1. For sheet C302 - 303: Please label drainage slope for rip rap swale.
Sheet 13
1. TSM 2-01.11.0 - Please provide erosion protection at end of earthen channel on east side of parking lot.
Sheet 14
1. Please label drainage slope and flow direction at main entrance public road.
2. For all sheets: Please label existing street name and whether it is "Public or Private" street.
Sheet 16
1. Please label dash line that connect to septic tank at Sewer Key Notes 7.
Sheet 17
1. Sheets C401 AND C402: ADD NOTE TO PLANS INDICATING MINIMUM COVER DEPTH FOR NORMAL CONDITIONS (UNDER PAV'T AND NON-PAVED AREAS) AND WASH CROSSINGS.
Sheet 23
1. Detail 7 - Please check spelling for "SPECIFICATION".
2. Detail 9 - Currently call-out "Hand Placed D50=6" Rip Rap Per DTL 8" which is a Curb Access Ramp. Please revise call-out to be "Hand Placed D50=6" Rip Rap Per DTL 3 This Sheet".
Sheet 34
1. The proposed tree is located on the slope of earthen basin.
Sheet 39
1. Please move overlapped text.

SWPPP Comments:
Sheet SW03
1. Please label: -Boundary of property, existing structures; Areas of soil disturbed and areas that will not be disturbed; Location of all potential pollutant-generating activities, on-site material, waste, stockpile, or equipment storage areas and other supporting activities; Label 75' erosion hazard setback.
2. Please indicate distance and direction to nearest receiving waters and include this in the cover sheet location map.
Sheet SW04
1. Please move overlapped text on top of the Retention/Detention basin.
2. Please provide erosion protection at end of earthen channel (east side of parking lot).
3. Please provide outlet protection for the first flush basin, perimeter control at the tops and toes of basin, and perimeter control for west swale (parking lot flows into it).
4. Please provide perimeter control at the toes of basin for the Retention/Detention Facility.

Drainage Comments:
1. Table 7 - Basin Results shown for the Existing and Post Conditions are not comparing the same drainage areas. Existing Q100=155.61 per Table 1 and Post Q100=203.3 cfs per Table 2. Please revise as necessary.
2. Apdx D - Please update Drainage Area IDs on Existing Conditions Watershed Map.
3. Apdx G - Please provide sizing calculations and parameters for outlet protection at culverts.
4. Apdx G - Worksheet for Riprap Section A-A shows roughness coefficient of 0.030 was used in calculation. Please refer to Table 8.1 in the Standards Manual for Drainage Design and Floodplain Management or describe why values differ for Manning's n coefficients.
5. Apdx G - Worksheet for Sections B-B, C-C & D-D show roughness coefficient of 0.020 were used in calculation for Earthen Channel. Please refer to Table 8.1 in the Standards Manual for Drainage Design and Floodplain Management or describe why values differ for Manning's n coefficients.
6. Apdx G - Curb Opening Calculations. Please indicate what standards or equations are shown for Curb Opening calculation.

Review and Comments provided by third party engineer reviewers under contract with the City of Tucson. For Questions or Concerns contact:
Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/22/2021 SBEASLE1 COT NON-DSD REVIEW Approved 03/22/21 The Transit Services Division and Sun Tran have no comments.
Thank you,

Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558
03/24/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 dentification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will may be needed and should contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number DP21-065 on each sheet.

Ensure that Zoning, Engineering comments and concerns are addressed prior to landscape section approval.

Additional comments may apply
03/24/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/25/2021 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change March 24, 2021

RE: DP21-0065 /Site/Grading/SWPPP - Tucson Police Department, 1st submittal, Received March 18, 2021

Thank you for the opportunity to comment on DP21-0065 /Site/Grading/SWPPP – Tucson Police Department; 1st Submittal, a development package application for a 14.3 acre site, located east of South Wilmot Road and south of the existing City of Tucson Policy Academy. The property is zoned Rural Homestead Zone (RH), with the proposed use being protective services for the storage of vehicles and the processing of evidence.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this proposed project resulted in the following responses:
1. Your proposed structure exceeds an instrument approach area by 138 feet and aeronautical study is needed to determine if it will exceed a standard of subpart C of 14CFR Part 77. The FAA, in accordance with 77.9, requests that you file.

2. Your proposed structure is in proximity to a navigation facility and may impact the assurance of navigation signal reception. The FAA, in accordance with 77.9, requests that you file.

3. The FAA requests that you file


The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.

Conditions of approval:
The applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp”

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully,

Scott Robidoux, C.M. , Senior Airport Planner
Tucson Airport Authority
03/25/2021 JPEELDA1 COT NON-DSD FIRE Approved
03/30/2021 NMARTEL1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Nicholas Martell
Planner

PROJECT:
Development Package (1st Review)
DP21-0065

TRANSMITTAL DATE: April 6, 2021

DUE DATE: April 6, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is March 30, 2022.







1. 2-06.4.4.C - Identify all Section, township, and range; section corners on the location map
2. Please add the Development Package number DP21-0065 to the title block
3. 2-06.4.8.A - Provide site boundary information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system to the site plan
4. 2-06.4.8.B - Ensure all easements are drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status.
5. 2-06.4.8.C - Please add the following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.
6. 2-06.4.9.F - Add all existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way).
7. 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.


8. 2-06.4.9.H.5.a - For the parking calculation, change the proposed use to Protective Service. The parking requirement for the Civic Use Group is 1 space per 300 square feet of GFA. Please adjust the parking calculations to reflect the parking for the civic use group.
9. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. Bike parking within the Civic Use Group is required at 1 space per 8,000 sq ft. GFA short term, and 1 space per 12,000 sq ft GFA long term.
10. 2-06.4.9.I - Show all right-of-way dedications on or abutting the site and label.
11. 2-06.4.9.O - Show all applicable building setback lines. The setback for a structure in the RH zone for a nonresidential use adjacent to a residential zone is 4 times the height of the structure.
12. 2-06.4.9.R - Show on-site pedestrian circulation and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.
13. 2-06.4.9.S - Show existing or proposed pedestrian circulation along abutting rights-of-way. Such sidewalks must comply with accessibility requirements for the physically disabled and the design criteria in Section 10-01.0.0, Street Technical Standards, of the Technical Standards Manual.



If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/02/2021 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved 04/02/21
No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 837-8040
04/06/2021 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
04/13/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: April 13, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP21-0065
DESCRIPTION: Site/Grading/Swppp - Tucson Police Department. New evidentiary processing/storage building and associated vehicle storage yard. 10505 S WILMOT RD

Fees Paid: See payment receipt attached.

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Thank you.

Sharon Beasley
Permit Specialist

City of Tucson, Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard the automatic reply you will receive: "This email account...")
04/14/2021 SBEASLE1 COT NON-DSD TRAFFIC Approved Approved 04/14/21.

David Stiffey
Transportation and Mobility
City of Tucson
04/26/2021 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The TEP FACILITIES MAP can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

April 23, 2021

SUBJECT: City of Tucson Police Department Evidentiary Vehicle Storage Yard, DP21-0065

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted March 24, 2021. There do not appear to be any conflicts.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300.
Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Ms. Bianca Maubach
New Business Project Manager
P. O. Box 711 (OH 204)
Tucson, AZ 85702
520-307-3864
Should you have any technical questions, please contact the area Designer Erik Reed at (520) 991-5372.
Sincerely,
Conor Mahoney, Office Support Assistant
TUCSON ELECTRIC POWER, Design/Build