Permit Number: DP21-0051
Parcel: 10408051D

Address:
4565 N ORACLE RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0051
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 SBEASLE1 START PLANS SUBMITTED Completed
03/03/2021 SBEASLE1 COT NON-DSD REVIEW Approved 03/03/21 The Transit Services Division and Sun Tran have no comments.
Thank you,

Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558
03/11/2021 JVINCEN1 COT NON-DSD FIRE Approved
03/19/2021 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP21-0051

1) Clarify if the patio area is part of the use area and update waste stream calculations
2) For the pedestrian path on the northside of the patio, show that a minimum 4' pedestrian path is being maintained. It is not clear if the patio area is part of the pedestrian path.
3) Keynote 28 on sheet appears to reduce the pedestrian circulation path to below 4' provide a dimension for the clear are and update as needed
4) For the western most parking spaces, update planting/landscape plan to affod 2.5' of vehicle overhang without impacting proposed vegetation
5) Provide site visibility triangles at the driveway exit onto Oracle Rd. The provides site visibility triangle appears to be looking for northbound traffic instead of northbound traffic.
6) Update drainage statement to provide a proposed conditions site exhibit

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
03/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/31/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 I dentification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number DP21-051 on each sheet.

Ensure that Zoning, Engineering comments and concerns are addressed prior to landscape section approval.

Additional comments may apply
04/05/2021 AWARNER1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination

FROM: Anne Warner, RLA
PDSD Zoning Review Section

PROJECT: Dutch Bros.
Development Package (1st Review)
DP21-0051

TRANSMITTAL DATE: April 2, 2021
DUE DATE: March 30, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. The one-year expiration date for this project is March 3, 2022.

2-06.3.0 Formatting

1. 2-06.3.10 – Legend on cover page is missing water harvesting area symbol and description, please add.
2. 2-06.4.3 - add relevant case numbers DP21-0051, C9-82-48 (original City zoning), adjacent to the title block on each sheet.
3. 2-06.4.8.C – Oracle right-of-way width is 200’, ½ right-of-way is 100’, revise detail on sheet 6. Adjust future sight triangles, right-of-way, curbs, sidewalks, as necessary.

2-06.4.0 Content

4. 2-06.4.7.A.6 – In accordance with the Gateway Corridor Zone, new utilities shall be placed underground.
5. 2-06.4.7.A.8.d – As the proposed Dutch Bros is part of a larger site, the calculations should encompass the entire site, whether existing or proposed. The whole site, under same ownership, includes the parcels to the north and west. Please provide calculations that include all of these parcels.
6. 2-06.4.9.H.5.a – The typical parking space detail on sheet 6 does not match the dimensions shown on the site plan. All parking spaces, except for ADA spaces should be 8.5’ x 18’. The existing parking detail shows substandard parking dimensions, please indicate and show that all parking will meet the UDC or a Parking Design Modification Request (PDMR) shall be sought. A PDMR must be approved prior to the Development Plan approval. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5769#JD_UDCSec.7.4.10
If the project is being phased, calculations must show that, at each phase, requirements are being met.
7. 2-06.4.9.Q - Add the specific use proposed within the footprint of the building.
8. 2-06.4.9.W - Key Note 27 & 28 are mislabeled, 27 is the monument sign location and 28 is the menu board. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.
9. Please provide a copy of the cross-access agreement.

If you have questions or comments, please email Anne Warner, RLA at anne.warner@tucsonaz.gov or call 520 837-4969
04/07/2021 JVINCEN1 COT NON-DSD TRAFFIC Approved 04/07/21
I don’t have any concerns or issues with this review. Regarding any traffic impact, everything with this site is remaining existing. Thanks

David Stiffey
City of Tucson
04/07/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: April 7, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP21-0051

DESCRIPTION: Site/Grading/Swppp - Dutch Brothers, new coffee shop with drive-thru.

FEES DUE: $ 2,439.02
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If amount isn't correct, check back in a few hours after data is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes
6- Click Continue

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title your 2nd submittal documents according to this example:
2_Comment Response Letter, 01.01.21

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov