Permit Number: DP21-0040
Parcel: 121091680

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0040
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2021 SBEASLE1 START PLANS SUBMITTED Completed
03/05/2021 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP21-0040

1) Show that the existing driveway apron will be update to PAG detail 207 and the pedestrian path across the apron meets ADA requirement

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
03/16/2021 JPEELDA1 COT NON-DSD FIRE Approved
03/18/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Tucson Water Well Site B-052B
Development Package (1st Review)
DP21-0040

TRANSMITTAL DATE: March 23, 2021

DUE DATE: March 18, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is February 18, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0040, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.1 – Sheet 3 “ZONING AND LAND USE NOTES, PROPOSED ZONING IS R-1, SPECIAL EXEMPTION” revise “EXEMPTION” to read “[2] Zoning Examiner Special Exception Procedure, Section 3.4.3”

3. COMMENT: 2-06.4.7.A.6.a – Once the Special Exception process is approved provide the T21SE#### adjacent to the title block on all sheets and provided a general note stating the Special Exception case number date of approval, and if applicable any conditions of approval.

2-06.4.7.A.8 - For development package documents provide:

4. COMMENT: 2-06.4.7.A.8.b – Provide a lot coverage calculation on the plan that meets the requirement of UDC Article 6.4.3. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 ZONE, the maximum lot coverage is 70%.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

5. COMMENT: 2-06.4.9.O – Clearly indicate on the plans how the requirements of UDC Use Specific Standards are met. It does not appear that Use Specific Standard 4.9.11.A.1 & .2 are met.

6. COMMENT: 2-06.4.9.O – Clearly indicate on the plans how the requirements of UDC Use Specific Standards are met. It does not appear that Use Specific Standard 4.9.11.A.9 are met


If you have any questions about this transmittal, please contact Elisa Hamblin, Elisa.Hamblin@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/23/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

The Development Package will may be needed and should contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number DP21-0040 on each sheet.

Landscape section cannot approve the development package until the special exception review is complete.

Ensure that Zoning, Engineering, and Design Professional comments and concerns are addressed,
03/24/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: March 24, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP21-0040
DESCRIPTION: Site/Grading - Equip Well B-052B, City of Tucson Water.
1937 N NANCY ROSE BL

FEE BALANCE: $0 (zero) Thank you for the payment. See attached receipt.

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard the automatic reply you will receive: "This email account is not...")
03/24/2021 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed 03/24/21 Passed per John Beall: "We have reviewed PDP, etc."

email: John.Beall@TucsonAz.gov
Planning and Development Services
Tucson, AZ