Permit Number: DP21-0018
Parcel: 10607006B

Address:
1019 W PRINCE RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0018
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2021 SBEASLE1 START PLANS SUBMITTED Completed
04/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Fire Station #8
Development Package (2nd Review)
DP21-0018

TRANSMITTAL DATE: May 3, 2021

DUE DATE: May 5, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 21, 2022.

2-06.4.9 - Information on Proposed Development

1. Zoning acknowledges that a copy of the unapproved Consolidation Request Form was provided with this submittal. Provide a copy of the approved Consolidation Request Form or a letter from the Pima County Assessor’s Office stating that the combo is in process with your next submittal. If all other review agencies approve this DP and this is the only remaining comment Zoning will put a hold on the Certificate of Occupancy for building permit T21CM01954. COMMENT: 2-06.4.9.E - As this site is comprised of four (4) parcels a lot combination is required. Provide a copy of the approved Pima County Combo Request for with your next submittal.

2. Zoning acknowledges that an MS&R Modification Request, T21SA00116, has been submitted but until it is approved Zoning cannot approve the DP. Once approved provide the MS&R Modification Request case number adjacent to the title block on all sheets and provide a general note stating the case number, date of approval, and if applicable any conditions of approval. COMMENT: 2-06.4.9.J – As Prince is designated on the COT MS&R map MS&R requirements apply, see UDC Article 5.4.2. That said either the site needs to be developed to meet the future right-of-way, or a future development package, meeting the requirements of AM 2-06, showing how the site will meet code when the road widening occurs or a MS&R Right-Of Way Use Modification request, UDC Article 5.4.7, must be submitted and approved.

Once the MS&R Modification Request has been approved and the required information has been provided on the DP resubmit the plans and send an email to Elisa Hamblin request an expedited review.

If you have any questions about this transmittal, please contact Elisa Hamblin, Elisa.Hamblin@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/11/2021 LOREN MAKUS ENGINEERING REVIEW Approved
05/17/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change
05/17/2021 SBEASLE1 LANDSCAPE REVIEW Needs Review