Permit Number: DP21-0018
Parcel: 10607006B

Address:
1019 W PRINCE RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0018
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2021 SBEASLE1 START PLANS SUBMITTED Completed
02/10/2021 SBEASLE1 COT NON-DSD REVIEW Approved 02/10/21 The Transit Services Division and Sun Tran have no comment. Transit services will not be affected.
Thank you,
Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558
02/18/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length. For example, assuming that the cleanout for the 6” building sewer downstream of the sand/oil separator has a rim elevation of 2318’ and an invert of 2314.67’, the maximum distance to the next cleanout would be approximately 96’. Reference: Section 708.1.1, IPC 2018.
2. Provide a cleanout immediately prior to entering the right of way. Reference: Pima County Standard Detail RWRD 401.
02/19/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Fire Station #8
Development Package (1st Review)
DP21-0018

TRANSMITTAL DATE: February 19, 2021

DUE DATE: February 22, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 21, 2022.

Zoning’s review is based on sheets, C1.0 – C9.2.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.7 – The project-location map shall be provided in the upper right corner of the cover sheet. See requirements below.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0018, adjacent to the title block on all sheets.

3. COMMENT: 2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three-inch equals one mile, and provide the following information.

4. COMMENT: 2-06.4.2.A – Show the subject property approximately centered within the one square mile area;

5. COMMENT: 2-06.4.2.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

6. COMMENT: 2-06.4.2.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

7. COMMENT: 2-06.4.9.E - As this site is comprised of four (4) parcels a lot combination is required. Provide a copy of the approved Pima County Combo Request for with your next submittal.

8. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.F.2.a.(1) Access lanes and PAALs must be setback at least one foot from: An open structure , such as a carport or covered pedestrian access path as measured from the closest part of the structure or roof overhang. That said the covered parking called out under reference note 22 needs to be setback 1’ from the PAAL.

9. COMMENT: 2-06.4.9.H.5.a – The required number of vehicle parking spaces listed under the parking calculation is not correct and should be listed as 25. Per UDC Article 7.4.3.G When the calculation of required motor vehicle and bicycle parking spaces results in a fractional number, a fraction of one-half or more is adjusted to the next higher whole number, and a fraction of less than one-half is adjusted to the next lower whole number.

10. COMMENT: 2-06.4.9.H.5.a – The number of required accessible vehicle parking spaces is not correct and should be 2, 1 being van accessible, see 2018 IBC Chapter 11, Table 1106.1 26 to 50 parking spaces provided requires 2 accessible spaces.

11. COMMENT: 2-06.4.9.J – As Prince is designated on the COT MS&R map MS&R requirements apply, see UDC Article 5.4.2. That said either the site needs to be developed to meet the future right-of-way, or a future development package, meeting the requirements of AM 2-06, showing how the site will meet code when the road widening occurs or a MS&R Right-Of Way Use Modification request, UDC Article 5.4.7, must be submitted and approved.

12. COMMENT: 2-06.4.9.R – Per TSM Section 7-01.3.3.B provide the required pedestrian path to the trash enclosure.

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/22/2021 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
02/23/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package should contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number DP21-00018 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comments may apply
03/01/2021 JPEELDA1 COT NON-DSD FIRE Approved
03/10/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Site is within a critical basin. Provide a complete drainage report providing retention and detention analysis for critical basin projects. Provide 5-year threshold retention and show 15 percent reduction in peak discharge in 2-, 10 and 100-year events. Water harvesting may be counted to contribute to retention and detention.
2. Revise the grades on the site to demonstrate drainage to water harvesting basins. For example the basin adjacent to the south property line will not receive runoff other than direct rainfall.
03/11/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: March 11, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP21-0018
DESCRIPTION: Site/Grading/SWPPP - City of Tucson Fire Station No. 8, new construction, 1025 W PRINCE RD

FEES DUE: $ 2,213.68
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal.
ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If information is not available or amount isn't correct, check back in a few hours after data is updated.
(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes
6- Click Continue

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.