Permit Number: DP21-0004
Parcel: 13604818A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0004
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2021 SBEASLE1 START PLANS SUBMITTED Completed
02/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Filiberto’s / Black Rock Coffee
Development Package (1st Review)
DP21-0004

TRANSMITTAL DATE: February 3, 2021

DUE DATE: February 09, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 12, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0004 , adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.6.a – As Pantano Pw and Golf Links Rd are designated on the COT MS&R plan/map, Pantano as an Arterial and Golf Links as an Arterial Gateway provide a general note on the cover sheet stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R) & UDC ARTICLE 5.5 GATEWAY CORRIDOR ZONE (GCZ).”

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

3. COMMENT: 2-06.4.8.C – Provide the following information for Pantano Pw, right-of-way width, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. COMMENT: 2-06.4.9.E – If you are going to show the “NEW LOT LINE BY PLAT” on the plan provide the distance and bearing. Also, the plat will need to be approved prior to approval of the DP. The cross-access agreement will also need to be recorded prior to approval.

5. COMMENT: 2-06.4.9.H.5 – Show and dimension the required stacking spaces for each drive-through, see UDC Article 7.4.7.

6. COMMENT: 2-06.4.9.O – The setback requirements shown under “SETBACKS, LANDSCAPE BORDERS AND SCREENING” note 1 are not correct. Per the definition of Established Area Setback any street designated on the MS&R plan is considered as Developing Area Setback. That said the street perimeter yard setbacks should be based on UDC Article 6.4.5.C.2 and Table 6.4.5.C-1 and should be listed as 21’ or the height (H) of the proposed exterior building wall, greater of the two, measured from the back of curb.

7. COMMENT: 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Also provide a general note stating “ALL SIGNAGE REQUIRES SEPARATE PERMITS”

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/11/2021 ZELIN CANCHOLA COT NON-DSD TRAFFIC Reqs Change DP21-0004
February 11, 2021
Zelin Canchola
Transportation and Mobility Engineering

The following requires change on plan:

The driveway along Golf Links Rd requires a 25 foot curb return radius, not a apron.
02/22/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change 4.1 Identification and Descriptive Data

ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number and DP21-0004 on each sheet.

Ensure that Zoning comments are addressed prior to landscape section approval.
02/24/2021 JPEELDA1 COT NON-DSD FIRE Approved
03/03/2021 SBEASLE1 COT NON-DSD REVIEW Approved 03/03/21 The Transit Services Division and Sun Tran have no comments.
Thank you,

Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558
03/10/2021 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP21-0004

1) For the maneuvering area in front of the trash enclosure it looks like the 14' wide areas are small compared to the overall width (28') of the enclosure itself update as needed
2) Show on plans the pedestrian circulation path to the proposed trash enclosure
3) Show on plans that curb access ramps located in the right of way, around the entire site, will be updated to PAG standard 207 and that sidewalks will be updated to PAG 200
4) Show on plans the cross slope and running slope for both proposed accessible parking space
5) Sheet 7. Provide a detail including cross slope and spot grades for the pedestrian path across the driveway entrance S Pantano Pky
6) Per (TSM) section 10-01.3.2.C. At the intersections of streets with other streets or collector or arterial streets with PAALs/Driveways, the curb lines will be connected with a curve having the minimum radius shown in Figure 6, measured at the face of the curb. Update the driveway entrance/exit onto S Pantano Pky and E Golf Links Rd as needed
7) Add DP21-0004 to cover of drainage report
8) Page 14 of the drainage report Figure 2 Offsite Watersheds. Two OS-1's are shown, one on the N side and one on the soutside of E golf links. Please update as needed to show these are different watershed
9) For the sheet flow across the subject property (from the location of CB1) update drainage report to indicate the depth of water across the subject parcel.
10) For the inlet of the existing 18" RCP at the driveway on S Pantano parkway, provide invert elevations and spot grades showing how the water harvesting/drainage channel enteres the RCp
11) There is an 18" RCP crossing S Pantano Pkwy (near the inlet location of the previously mentioned RCP). This cannot be found or seen, and is not mentioned in the drainage report

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
03/10/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: March 10, 2021 Returned for Corrections

PERMIT/ACTIVITY: DP21-0004
DESCRIPTION: SITE/GRADING - Filiberto's Restaurant and Black Rock Coffee drive-thru.
8601 E GOLF LINKS RD

FEES DUE: $ 1,025.00 Thank you for the partial payment.
A payment is required before your next submittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If information is not available or amount isn't correct, check back in a few hours after data is updated.
(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes
6- Click Continue

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard the automatic reply you will receive: "This email account is not...".)