Permit Number: DP21-0003
Parcel: 11103064C

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0003
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2021 SBEASLE1 START PLANS SUBMITTED Completed
02/04/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Development Services Department Zoning Review

PROJECT: Country Club Multifamily
Development Package (1st Review)
DP20-0003

TRANSMITTAL DATE: February 4, 2021

DUE DATE: February 10, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 11, 2022.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0003, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.6.a - As Country Club Rd is designated on the COT MS&R plan/map as an Arterial provide a general note on the cover sheet stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R).”

2-06.4.7.A.8 - For development package documents provide:

3. COMMENT: 2-06.4.7.A.8.b – Per UDC Article 6.3.3.D Multifamily development is considered a Nonresidential Use for Dimensional Standards. That said per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 Zones, C-1 Zone Lot coverage is not applicable. Remove “ZONING & LAND USE NOTE” 6 from the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. COMMENT: 2-06.4.9.A – As this site is made up of three (3) parcels, 111-03-064C, 111-03-064D & 111-03-064E, a lot combination is required. Provide a copy of the approved Pima County Combo Request form with you next submittal.

5. COMMENT: 2-06.4.9.H.2 - Show future sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

6. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.D, Figure 7.4.6-A and Table 7.4.6-1 the minimum PAAL with when accessing 90-degree parking is 24’-0. Zoning acknowledges that you are requesting and administrivia reduction in width but a TSMR is not the correct process. Reduction of PAAL with is done via a Parking Design Modification Request (PDMR) see UDC Article 7.4.10. Per UDC Article 7.4.10.D.10 the request can only reduce the width of a PAAL by 5%. Your request exceeds the 5% and Zoning would not be able to approve the PDMR.

7. COMMENT: 2-06.4.9.J - If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc.)

8. COMMENT: 2-06.4.9.O – The setback requirements shown under “SETBACKS, LANDSCAPE BORDERS AND SCREENING” note 1 are not correct. Per the definition of Established Area Setback any street designated on the MS&R plan is considered as Developing Area Setback. That said the street perimeter yard setbacks should be based on UDC Article 6.4.5.C.2 and Table 6.4.5.C-1 and should be listed as 21’ or the height (H) of the proposed exterior building wall, greater of the two, measured from the back of curb.

9. COMMENT: 2-06.4.9.Q – Per UDC Article 6.3.3.D Multifamily development is considered a Nonresidential Use for Dimensional Standards. That said per UDC TABLE 6.3-4.A: DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 Zones, C-1 Zone the maximum allowed height allowed is 30’. Revise “ZONING & LAND USE NOTE” 7 to show the correct height.

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/08/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/10/2021 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

02/10/21 Country Club Multifamily, DP21-0003, 1st submittal, is being Returned for Corrections.
The attached pdf contains Addressing’s comments. Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV 1 st Floor
Tucson, AZ 85701
(520) 724-7570
02/11/2021 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved DP21-0003
February 1, 2021
Zelin Canchola
Transportation and Mobility Engineering

Recommend approval of development plan.

Ensure a unobstructed walkable area along frontage of Country club Road is maintained.
02/17/2021 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change 4.1???Identification and Descriptive Data

ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number and DP21-0003 on each sheet.



Landscape Borders

Located on Site

Street landscape borders must be located entirely on site , except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacentright-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets .

The landscape borders are not located on site revise as necessary

Canopy Trees in Vehicular Use Areas

General Standards

Within a vehicular use area , one canopy tree is required for each four motor vehicle parking spaces or fraction thereof.

(1) The canopy trees must be evenly distributed throughout the vehicular use area . Every parking space must be located within 40 feet of the trunk of a canopy tree (as measured from the center of the tree trunk).

(2) Fifty percent of the trees required for landscape borders located within ten feet of the paved portion(s) of a vehicular use area may be counted towards both the minimum parking lotcanopy tree standard and the landscape border canopy tree standard.

Show compliance with Canopy tree requirements.

Ensure that Zoning comments are addressed prior to landscape section approval.
02/25/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Sheet 1
1. Technical Standard Modification Request and Design Development Options require approval before the Development Package can be approved. Add case number reference to lower right corner of each sheet.
2. Zoning and Land Use Notes contain duplicate notes 6 and 7. Renumber as needed.
Sheet 3
3. TSM 8-01.5.3 Provide minimum 36' inside turn radius and 50' outside turn radius for collection vehicles and/or show vehicle maneuverability and access route fully dimensioned.
4. Add contour intervals to all north arrow and scale blocks.
5. List the specific use with the square feet and height of each building.
Sheet 4
6. Provide detail for bubbler and demonstrate adequate percolation rate to avoid ponded water in bubbler.
Sheet 5
7. TSM 8-01.5.2 Provide a 2% min drainage slope away from the dumpster enclosure.
Drainage Report
8. Cover - Please fill out remainder of case number.
9. Section 1.0D - Please contact PC Flood Control to check the status of the Christmas Wash FLO-2D study, which should have been completed within the last few years. Verify if the study results impact this project.
10. Section 3.0 - Please verify if the Pima County Regional Flood Control district has 2D mapping covering the project area as part of their Christmas Wash study.
11. Section 4.0 A - Please describe how the "bubbler" systems will be prevented from getting clogged and efforts necessary to prevent standing water in the pipes which could lead to mosquito problems or result in undesirable smells from stagnant water.
12. Section 4.0 A - Please explain how the 1/2" notches prevent standing water if the concrete sidewalk to the north acts as the highest elevation resulting in ponding
13. Figure 2a - Please include a bar scale.
14. Figure 2a - Please include watershed flow length, soils type, contour labels, aerial photograph
15. Figure 2a - Please label the Rillito River
16. Figure 2b - Please identify all adjacent parcels
17. Figure 2b - Please include a bar scale
18. Figure 7 - Please call out project area on exhibit.
19. Roof Drainage Calculations - Please provide explanation/supporting documentation for 9.6 in/hr intensity used.
20. Outflow weir calculation sheet - Please provide equation source and weir coefficient source if separate from equation.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/02/2021 MROSS2 COT NON-DSD FIRE Approved Automatic sprinkler system and fire alarm system plans shall be defered submitals to the fire department.
03/12/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: March 12, 2021
Returned for Corrections

PERMIT/ACTIVITY: DP21-0003
DESCRIPTION: SITE - Country Club Multifamily, 3540 N COUNTRY CLUB RD

FEES DUE: $ 2,232.37
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If information is not available or amount isn't correct, check back in a few hours after data is updated.
(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes
6- Click Continue

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

For all NEW development package submittals on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard the automatic reply you will receive: "This email account is not...")
03/12/2021 SBEASLE1 COT NON-DSD REVIEW Approved 03/12/21 The Transit Services Division and Sun Tran have no comments on DP21-0003 at this time.
Thank you,

Christopher Blue
Transit Services Coordinator | Transit Services Division
Department of Transportation & Mobility
C: 520.260.9558