Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP21-0002
Parcel: 114511800

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP21-0002
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. With the new design, buildings 156 and 160 require a backwater valve but do not have one. Buildings 162, 163, and 164 are shown with backwater valves but they cannot have backwater valves. [Initial comment: Per Section 714.1, IPC 2018, as amended by the City of Tucson, "Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor." A cleanout is not a manhole cover so buildings 165, 166, 167, 168, and 169 do not require backwater valves.]
2. A new manhole is shown on sheet 84 of 123, located between manhole #21 and Manhole #19. Provide the rim elevation and inverts of the manhole. Reference: Section 107.2.1, IBC 2018.
3. Clarify how buildings 157, 158, and 159, on sheet 83 of 123, are connected to the private sewer collection system. Reference: Section 107.2.1, IBC 2018.
08/23/2022 SBLOOD1 ENGINEERING REVIEW Approved
09/23/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change email from: COTDSDPermits
To: Bill, Billy Box, Rob
09/23/2022

REVISION REVIEW NOTICE
Returned for Corrections: DP21-0002
Site/Grading/Floodplain - Casitas on Catalina, Phase One.
9125 E CATALINA HY

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on the blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD documents to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set pages
- Documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)


Sharon Beasley, Certified Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)
09/29/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Approved email from: Nicholas Jordan on behalf of Addressing
To: CDRC
09/28/2022

The revisions to DP21-0002 are simple enough and I can reflect the changes in the map. I’m happy to approved the revision.
Please let me know if the layout changes so that I can make parallel changes.
Thank you

Nicholas Jordan
Site Review Project Manager - Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-9623