Permit Number: DP21-0002
Parcel: 114511800

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP21-0002
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2022 STEVE SHIELDS ZONING REVIEW Approved
03/31/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Private sewers 8-inches and larger require manholes, not cleanouts. Reference: Section 708.1.2, IPC 2018.
2. Per Section 714.1, IPC 2018, as amended by the City of Tucson, "Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor." A cleanout is not a manhole cover so buildings 165, 166, 167, 168, and 169 do not require backwater valves.
04/05/2022 JPEELDA1 COT NON-DSD FIRE Approved
04/13/2022 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Email from: Howard Dutt
To: CDRC
Mon 4/11/2022 9:51 AM

No existing or proposed Tucson Parks and Recreation facilities are affected by these revisions.

Howard Dutt, RLA
Project Manager/Landscape Architect

Parks and Recreation | City of Tucson
Howard.Dutt@tucsonaz.gov
main 520.631.2030
04/15/2022 DSTIFFE1 COT NON-DSD TRAFFIC Approved
04/29/2022 SBEASLE1 COT NON-DSD REVIEW Approved Email from: Eric Latto
To: CDRC
Fri 4/29/2022 4:06 PM

We have a bus stop south of the condo complex at Catalina Hy/Tanque Verde. I don’t see any issues here.

Eric Latto MPA, Transit Services Coordinator
Department of Transportation and Mobility
Direct: 520-954-3717

City of Tucson
149 N. Stone Avenue, Second Floor
Tucson, AZ 85701
05/02/2022 PETER MCLAUGHLIN COT NON-DSD COMMUNITY PLANNING Completed
05/09/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Per Admin Manual Section 2-06.4.1 On the cover sheet provide the name, mailing and email addresses, and phone number of the firm that prepared the Geotech Report.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
05/18/2022 AWARNER1 LANDSCAPE REVIEW Approved
06/14/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Bill Carroll
cc: Billy Box, Rob
Tue 6/14/2022 2:19 PM

REVISION REVIEW NOTICE
Returned for corrections, DP21-0002

Project Description: Site/Grading/Floodplain - Casitas on Catalina, Phase One. 9125 E CATALINA HY

REVISION FEES DUE: $ 924.00
$82.50/hour plus $16.50 Tech fee (Fire charges for two hours, not one)

ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
If amount doesn't match "Revision Fees Due", check back in a few hours after it is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5-Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff

Thank you.
Sharon Beasley, Certified Permit Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)

Email: PDSDinquiries@TucsonAz.gov
(for building permits and all other subjects)
06/14/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review