Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP21-0002
Parcel: 114511800

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP21-0002
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2021 SBEASLE1 START PLANS SUBMITTED Completed
04/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change While most of the backwater issues were resolved, seven buildings still require changes regarding backwater valves.
a. Building 48 does not require the installation of a backwater valve.
b. The following building do require the installation of a backwater valve: 78, 83, 104, 105, 108, and 110.
04/20/2021 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields

PROJECT: Casita Village on Catalina
Development Package (2nd Review)
DP21-0002

TRANSMITTAL DATE: April 20, 2021

DUE DATE: April 20, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 7, 2022.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

1. This comment was not fully addressed. Provide the Use Specific Standards for multifamily listed in UDC Table 4.8-2. COMMENT: 2-06.4.7.A.4 – General Site Note 21 the existing use is listed as “GENERAL COMMERCIAL SERVICES” but should be listed as RESIDENTIAL. Also, the proposed use should also list the applicable Use Specific Standards as listed in UDC Table 4.8-2, PERMITTED USES - URBAN RESIDENTIAL, Residential Land Use Group With Land Use Class/Type: Multifamily Development for the R-2 zone. You also list a proposed use of “RETAIL/GENERAL MERCHANDISE” as a proposed use. “RETAIL/GENERAL MERCHANDISE” is not an allowed use in the R-2 Zone.

2. Remove all references to “SITE COVERAGE” as site coverage does not apply to this site. Within the Lot Coverage Calculation provide a breakdown showing the building area and vehicle use area. COMMENT: 2-06.4.7.A.8.b – Provide a lot coverage calculation on the plan that meets the requirements of UDC Article 6.4.3. Per UDC Table 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2, R-2 zone the maximum lot coverage is 75%.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

3. This comment was not addressed. The provide “Consolidation Request From” is not fully filled out, no parcel numbers provided and there is no approval from Pima County. COMMENT: 2-06.4.8.A – As this site is made up of two (2) parcels, 114-52-008G & 114-51-1790, a lot combination is required. Provide a copy of the approved Pima County Combo Request form with the next submittal.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. This comment was not fully addressed. Sheet 25 the western most backup spur demonstrate that the required 3’ distance is provided from the back of spur to what appears to be bollards, see UDC Article 7.4.6.F.4.c.COMMENT: 2-06.4.9.H.5 – Fully dimension all back-up spurs shown on the plans, see UDC Article 7.4.6.F.4.

5. This comment was not address, provide the number provided. COMMENT: 2-06.4.9.H.5.d – Provide the number of short – and long – term bicycle spaces provided within the calculation.

6. Provided detail 3 sheet 73 does not address UDC Articles 7.4.9.B.1.d, .e, 7.4.9.B.2.a.b, .f . COMMENT: 2-06.4.9.H.5.d – Provide a short – term bicycle parking detail that demonstrates how the requirements of UDC Articles 7.4.9.B.1, .2 & 7.4.9.C are met.

If you have any questions about this transmittal, please Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/20/2021 SSHIELD1 LANDSCAPE REVIEW Approved
04/20/2021 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

Email from: Robin Freiman <Addressing@pima.gov>
To: CDRC
Tue 4/20/2021 11:52 AM

Casitas on Catalina, 2nd submittal, DP21-0002, is being Returned for Corrections by Pima County Addressing.

The attached pdf contains Addressing’s comments. Please let me know if you have any questions. Thank you,

Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701, (520) 724-7570
04/23/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. ADEQ has issued a new construction general permit. The current version must be included in the SWPPP report. The SWPPP checklist should also be updated to the current checklist.
2. Include rezoning conditions 9 through 12 in the list of rezoning conditions.
3. Provide approval for the driveway width from the Director of DTM.
4. Provide recordation information for the easements for the off-site basins.
5. Provide security barriers around basin DD and any other basin with a 100-year water depth greater than 2 feet.
04/29/2021 SBEASLE1 COT NON-DSD TRAFFIC Approved Email received from: DavidStiffey@TucsonAz.gov
To: CDRC
Thu 4/29/2021 6:04 AM

Approved. No comments.

City of Tucson
Transportation and Mobility
04/29/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email sent from: COTDSDPermits
To: B Carroll
Thu 4/29/2021 12:27 PM

Returned for Corrections
PERMIT/ACTIVITY: DP21-0002
DESCRIPTION: Site/Grading/Floodplain - Casitas on Catalina. 9125 E CATALINA HY

FEE BALANCE: $0 (zero) Thank you for the payment.

SEND YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your 3rd submittal documents according to this example:
3_Comment Response Letter, 01.01.21

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document


Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard any automatic reply you might receive)